beautypg.com

Locating the water heater, Clearances, Locating the water heater clearances – State SBL85 390 NE A User Manual

Page 9: Caution, Fire or explosion hazard

background image

9

Do not install this water heater directly on a carpeted floor. A fire

hazard may result. Instead the water heater must be placed on a

metal or wood panel extending beyond the full width and depth by

at least 3 inches in any direction. If the water heater is installed in a

carpeted alcove, the entire floor shall be covered by the panel. Also,

see the DrAINING requirements in MAINTeNANCe Section.
The water heater shall be located or protected so it is not subject

to physical damage by a moving vehicle.
Flammable items, pressurized containers or any other potential

fire hazardous articles must never be placed on or adjacent to

the water heater. Open containers or flammable material should

not be stored or used in the same room with the water heater.
The water heater must not be located in an area where it will be

subject to freezing.
locate the water heater near a floor drain. The water heater

should be located in an area where leakage from the water

heater or connections will not result in damage to adjacent area

or to lower floors of the structure.
When such locations cannot be avoided, a suitable metal drain

pan should be installed under the water heater. Such drain pans

should be fabricated with sides at least 2” deep, with length and

width at least 2” greater than diameter of the water heater and

must be piped to an adequate drain. The drain pan must not

restrict combustion air flow.

ClearanCes

This water heater is approved for installation on combustible

flooring in an alcove with minimum clearance from combustion

construction as indicated in Figure 7 and Table 4.
In all installations the minimum combustible clearances from

vent piping shall be 6” (15.2 cm). Vent piping passing through a

combustible wall or ceiling must be a continuous run (no joints)

and retain 6” (15.2 cm) clearance unless an approved reducing

thimble is used.
A service clearance of at least 24” (61 cm) should be maintained

from serviceable parts.
The units are approved for installation with side, rear and ceiling

clearances as indicated below:

taBle 4. minimum ClearanCes to ComBustiBle or

non-ComBustiBle ConstruCtion

Model

"A" right Side "b" left Side "C" back "D" Ceiling

All Models

0"

0"

0"

12"

0 cm

0 cm

0 cm

30.5 cm

loCating the water heater

Property Damage Hazard

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

When installing the heater, consideration must be given to

proper location. location selected should be as close to the

stack or chimney as practicable, with adequate air supply and as

centralized with the piping system as possible.

Fire or Explosion Hazard

Read instruction manual before

installing, using or servicing

water heater.

Avoid all ignition sources if you smell gas.

Do not store or use gasoline or other flammable vapors and

liquids in the vicinity of this or any other appliance.

Use only the gas shown on the water heater rating label.

Keep ignition sources away from faucets after extended

periods of non-use.

Maintain required clearances to combustibles.

Do not expose water heater controls to excessive gas

pressure.

There is a risk in using fuel burning appliances such as

gas water heaters in rooms, garages or other areas where

gasoline, other flammable liquids or engine driven equipment

or vehicles are stored, operated or repaired. Flammable

vapors are heavy and travel along the floor and may be

ignited by the water heater's igniter or main burner flames

causing fire or explosion. Some local codes permit operation

of gas appliances in such areas if they are installed 18" or

more above the floor. This may reduce the risk if location in

such an area cannot be avoided.

This manual is related to the following products: