beautypg.com

Table 7. technical data venting (continued) – State SBL85 390 NE A User Manual

Page 19

background image

19

taBle 7. teChniCal data Venting (Continued)

Model Sbl85390Ne(A)
Input: 390,000 btu/hr

Total Vent Height (Feet)

Vent connector size: 6 inches

6

8

10

15

20

30

50

100

Input (btu/hr)

Rise

Vent Connector Diameter (Inches)

390,000

1 Ft.

-

-

-

-

8

7

7

6

390,000

2 Ft.

-

-

-

8

8

7

7

6

390,000

3 Ft.

-

-

8

8

8

7

7

6

Number of Heaters

Combined Input (btu/hr)

Manifold and Common Vent Diameter (Inches)

2

780,000

12

12

12

10

10

9

9

8

3

1,170,000

16

14

14

14

12

12

10

9

4

1,560,000

16

16

16

14

14

14

12

10