Connecting the gas piping to the gas control valve of the water

heater can be accomplished by either of the two methods shown in

Figures 9 and 10.

sedIMent traps

A sediment trap shall be installed as close to the inlet of the water

heater as practical at the time of water heater installation. The

sediment trap shall be either a tee fitting with a capped nipple in the

bottom outlet or other device recognized as an effective sediment

trap. If a tee fitting is used, it shall be installed in conformance with

one of the methods of installation shown in Figures 9,10 and 11.

fIGure 9. Gas pIpInG wIth fleXIBle connector.

fIGure 10. Gas pIpInG wIth all

BlacK Iron pIpe to Gas control.

alternatIve sedIMent trap locatIon

fIGure 11.

Contaminants in the gas lines may cause improper operation of the

gas control valve that may result in fire or explosion. Before attaching

the gas line be sure that all gas pipe is clean on the inside. To trap any

dirt or foreign material in the gas supply line, a drip leg (sometimes

called a sediment trap) must be incorporated in the piping. The drip

leg must be readily accessible. Install in accordance with the “Gas

Piping” section. Refer to the current edition of the National Fuel Gas

Code, ANSI Z223.1/NFPA 54.

whIte-rodGers fuel conversIon

InstructIons froM natural Gas to

propane (l.p.) Gas

Fuel conversions shall be completed by a qualified service

agency in accordance with the detailed conversion instructions

and all applicable codes and requirements of the authority having

jurisdiction. The information in these instructions must be followed to

minimize the risk of fire or explosion and to prevent property damage,

personal injury or death. The qualified service agency is responsible

for the proper installation of this kit. The installation is not proper and

complete until the operation of the appliance is checked as specified

in the manufacturer’s instructions.

1. Read and follow detailed conversion instructions below and also

on the heater.

2. The conversion kit with necessary parts are in a bag attached to

the side of the water heater.

3. Shut off the gas supply to the water heater.

4. Remove the outer door.

5. Rotate the thermostat dial on the water heater control

counterclockwise (

) until the main burner ignites and burns

off all residual gas in the control and supply lines.

6. Rotate the thermostat dial clockwise ( ) back to the “PILOT

LIGHTING” position.

7. Turn the gas control knob “A” to “PILOT”. Depress knob slightly

and rotate to “OFF” position, see Figure 12.

fIGure 12.

8. Unplug wire from igniter assembly mounted to the top of the gas

valve.

This manual is related to the following products: