The water within the water heater tank expands as it is heated and

increases the pressure of the water system. If the relieving point of the

water heater’s temperature-pressure relief valve is reached, the valve

will relieve the excess pressure.

the temperature-pressure relief

valve is not intended for the constant relief of thermal expansion.

This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a

closed system have a by-pass and/or the system have an expansion

tank to relieve the pressure built by thermal expansion in the water

system. Expansion tanks are available for ordering through a local

plumbing contractor. Contact the local water supplier and/or a service

agency for assistance in controlling these situations.

note: to protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric unions

or couplings be installed on this water heater when connected

to copper pipe.

fIGure 5.

Figure 5 shows the typical attachment of the water piping to the

water heater. The water heater is equipped with 3/4 inch NPT water

connections.

note: If using copper tubing, solder tubing to an adapter before

attaching the adapter to the cold water inlet connection. do not

solder the cold water supply line directly to the cold water inlet.

It will harm the dip tube and damage the tank.

water pIpInG pressure test

This section is only for the manufacturer installing the water heater

when the installation is to comply with H.U.D. Standards.

When testing the water ways, H.U.D. Standards state:

“Water distribution system. All water piping in the water distribution

system shall be subjected to a pressure test. The test shall be made by

subjecting the system to air or water at 100 psi for 15 minutes without

loss of pressure.

when air pressure is used, the water heater shall

not be connected during the test”.

note: If water piping system is to be air pressure tested, the water

heater must be disconnected from the water piping system. Failure

to disconnect the water heater during air pressure testing of water

piping system could result

In death, serIous BodIlY InjurY,

or propertY daMaGe.

fIGure 6.

teMperature-pressure relIef valve