beautypg.com

State GS6 50 YOMT User Manual

Page 11

background image

11

This heater is provided with a properly certified combination

temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory

that maintains periodic inspection of production of listed equipment of

materials as meeting the requirements for Relief Valves for Hot Water

Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements

of ASME.

If replaced, the valve must meet the requirements of local codes, but

not less than a combination temperature and pressure relief valve

certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to

exceed the marked hydrostatic working pressure of the water heater

(150 psi = 1,035 kPa) and a discharge capacity not less than the water

heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be

removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into

the fitting of the water heater designed for the relief valve. Position

the valve downward and provide tubing so that any discharge will exit

only at any distance below the structural floor. Be certain that no

contact is made with any live electrical part. The discharge opening

must not be blocked or reduced in size under any circumstances.

Excessive length, over 30 feet (9.14 m), or use of more than four

elbows can cause restriction and reduce the discharge capacity of

the valve, see Figure 7.

No valve or other obstruction is to be placed between the relief valve

and the tank. Do not connect tubing directly to discharge drain unless

a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or

property damage, the relief valve must be allowed to discharge water

in quantities should circumstances demand. If the discharge pipe is

not connected to a drain or other suitable means, the water flow may

cause property damage.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the valve, or

have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.

• Shall be of material listed for hot water distribution.

• Shall be installed so as to allow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Shall terminate at an adequate drain.

• Shall not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually operated at

least once a year. Caution should be taken to ensure that (1) no one

is in front of or around the outlet of the temperature-pressure relief

valve discharge line, and (2) the water manually discharged will not

cause any bodily injury or property damage because the water may

be extremely hot.

If after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold water inlet

to the water heater, follow the draining instructions, and replace the

temperature-pressure relief valve with a new one.

fIGure 7.

fIllInG the water heater

Never use this water heater unless it is completely full of water. To

prevent damage to the tank, the tank must be filled with water. Water

must flow from the hot water faucet before turning “ON” gas to the

water heater.

This manual is related to the following products: