beautypg.com

0130-01-00 rev c, Contact information, Notice of copyright – Outback Power Systems IBR-2 User Manual

Page 4: Date and revision, Part number, Installing shunts

background image

Installing Shunts

Figure 9 Installing Shunts

Contact Information

Address:

Corporate Headquarters
17925 – 59

th

Avenue N.E.

Suite B
Arlington, WA 98223 USA

European Office
Hansastrasse 8
D-91126
Schwabach, Germany

Telephone:

+1.360.435.6030
+1.360.618.4363 (Technical Support)
+1.360.435.6019 (Fax)

+49.9122.79889.0
+49.9122.79889.21 (Fax)

Email:

[email protected]

Website:

http://www.outbackpower.com

Notice of Copyright

Integrated Battery Rack Installation Manual © August 2013 by OutBack Power Technologies.
All Rights Reserved.

Date and Revision

August 2013, Revision C

Part Number

900-0130-01-00 Rev C

To Install a Shunt or Shunts:

Up to three shunts may be installed for the use of a battery monitor such as the

FLEXnet DC. Perform the following steps before step 5 on page 2.
1. Remove the negative bus bar and cables from the left side of the rack (see right).

Unbolt the individual cables from the bus bar.

2. Three pairs of holes are located in the area where the bus bar is mounted (below,

left). A shunt can be placed over each set of holes. Each shunt has twin screws

(below, center) which can be used for mounting.

3. Reinstall the negative bus bar so that it mounts across the inner terminal of each

shunt (below, right). Each negative battery cable must not be bolted to the bus bar,

but should connect to the outer terminal of each shunt. However, the load cable
must connect to the negative bus bar.

4. The battery monitor’s voltage sensing wires must connect to the bus bars (positive

and negative), not the batteries.

Holes

Twin

Screws

This manual is related to the following products: