beautypg.com

Ee figure 7.), Energycell re battery rack instructions, Figure 7 bus and load cabling – Outback Power Systems IBR-2 User Manual

Page 3: Figure 8 protective shields (sides and front)

background image

EnergyCell RE Battery Rack Instructions

900-0130-01-00 Rev

C

3

Figure 7 Bus and Load Cabling

Figure 8 Protective Shields (sides and front)

10. Install the protective shields on the left and right sides of the battery

rack. Each shield has an edge which is designed to slide into a metal
tab on the rack. (See below.) Once the edge of the shield is secured,

the other side can be attached using M6 screws. (See the illustration

to the right.)

11. Install the protective shields on the front of each battery shelf. Make

certain to orient the shield correctly. The shield has an opening to

allow access to the circuit breaker for each set of batteries. (See the

illustration to the right.) If the shield is oriented incorrectly, it will
block access to the circuit breaker.

Machine

Screw

Machine

Screw

Machine

Screw

Circuit

Breaker

Shield

NOTE: The battery rack does not require
additional ventilation.

Provide adequate ventilation for the

room where the battery rack is installed.

7. Connect a ground cable to the battery rack.

The ground terminal is located directly below

the negative bus bar (see right). Make sure to

follow all applicable electrical codes when

grounding the rack.

8. The positive and negative bus bars have multiple

attachment points. The battery cables inside the

rack are already attached (see left). The user
should attach a fourth cable for battery loads (see

right). This load cable should be sized

appropriately. As shown to the right, the load

cable must be routed inside the enclosure using

one of the side openings. To complete the circuit,

the return load cable should connect to the bus
bar on the other side of the rack and also routed

inside the enclosure.

9. After load cables have been routed inside the enclosure, they should exit

using one of the conduit openings. The IBR-3-48-175 has six 2” conduit

knockouts on each side of the rack. The IBR-2-48-175 has four 2” conduit

knockouts on either side of the rack and three on top.

For users of the GS Load Center: The top knockouts are designed to

align with the GSLC cabling for ease of installation.

Load Cable

Cable entering

enclosure

Conduit

Ground

Terminal

The positive and negative bus bars are marked with “+” and “-“ symbols respectively.
The ground terminal is marked with the symbol.

This manual is related to the following products: