Three-Phase Stacking Only

The OutBack HUB is shipped from the factory setup for series (120/240 VAC split phase) and/or

parallel (120 VAC or 230 VAC single phase) stacking. If three-phase stacking is desired, the cover

must be removed and a jumper position changed. For three-phase stacking using a HUB 4:

1. Remove the black snap on wiring cover and all cables plugged into the HUB.

Label the cables to avoid confusion when

reconnecting.

2. Remove the four Phillips screws from the

bottom of the HUB.

3. Remove bottom cover and remove the four

Phillips screws holding the green PCB to

the upper cover.

PCB removed

Bottom cover removed

Jumper