Mechanical specifications, Environmental specifications, Specifications – Outback Power Systems GS3548E Operators Manual User Manual
Page 66
Specifications
64
Table 12
Electrical Specifications for Radian Models
Specification
GS7048E
GS3548E
DC Input Maximum Current (surge)
406.5 Adc
203.3 Adc
DC Input Maximum Current (short-circuit)
8975 Adc
4488 Adc
Battery Charger Maximum AC Input
30 Aac at 230 Vac
15 Aac at 230 Vac
Battery Charger Maximum DC Output
100 Adc
50 adc
DC Output Voltage Range (charging)
44 to 68 Vdc
44 to 68 Vdc
Auxiliary Output
0.7 Adc at 12 Vdc
0.7 Adc at 12 Vdc
Auxiliary Relay
10 A at 250 Vac or 30 Vdc
10 A at 250 Vac or 30 Vdc
Mechanical Specifications
Table 13
Mechanical Specifications for Radian Models
Specification
GS7048E
GS3548E
Inverter Dimensions (H x W x D)
71.1 x 40.6 x 22.2 cm
(28 x 16 x 8.75")
71.1 x 40.6 x 22.2 cm
(28 x 16 x 8.75")
Shipping Dimensions (H x W x L)
36.8 x 53.3 x 87.6 cm
(14.5 x 21 x 34.5")
36.8 x 53.3 x 87.6 cm
(14.5 x 21 x 34.5")
Inverter Weight
56.8 kg (125 lb)
37.2 kg (82 lb)
Shipping Weight
63.5 kg (140 lb)
42.6 kg (94 lb)
Accessory Ports
RJ11 (batt temp) and
RJ45 (remote)
RJ11 (batt temp) and
RJ45 (remote)
Non-volatile Memory
Yes
Yes
Neutral-Ground Bond Switching
No
No
Chassis Type
Vented
Vented
Environmental Specifications
Table 14
Environmental Specifications for Radian Models
Specification
Value
Rated Temperature Range (meets component specifications; however, please note
that the inverter output wattage is derated above 25°C)
–20°C to 50°C ( –4°F to 122°F)
Operational Temperature Range (functions, but does not necessarily meet all
component specifications)
–40°C to 60°C (–40°F to 140°F)
Storage Temperature Range
–40°C to 60°C (–40°F to 140°F)
IP (Ingress Protection) Rating of Enclosure
IP20
Environmental Category
Indoor unconditioned
Wet Locations Classification
Wet locations: No
Relative Humidity Rating
93%
Pollution Degree Classification
PD 2
Maximum Altitude Rating
2000 m (6561’)
Overvoltage Category (AC Input)
3
Overvoltage Category (DC Input)
1