General characteristics of Galaxy 5000 UPSs
INFORMATION
The operating temperature range is 32°F to 104°F (0°C to +40°C); for overload
conditions is 32°F to 86°F (0°C to +30°C). Optimum operating range is within 68°F
to 77°F (20°C to +25°C). Battery backup time is adversely affected by high and low
temperatures. It is significantly reduced at temperatures under 50°F (10°C). Above
77°F (25°C), battery service life is cut in half every 18°F (10°C). Above 104°F (40°C),
battery manufacturers no longer guarantee operation due to the risk of thermal
runaway.
UPS power in KVA
40
50
60
80
100
130
Normal AC input
Number of conductors
3 phases + ground
Reference voltage at Pn
432 V to 528 V
Reference frequency
45 Hz to 65 Hz
THDI
Typically 3% at Pn
Power factor
>0.99
Bypass AC input
Number of conductors
3 phases + ground
Reference voltage at Pn
432 V to 528 V
Reference frequency
45 Hz to 65 Hz
Load output
Number of conductors
3 phases
Set phase-to-phase voltages
480 V
Voltage variation
± 1%
Adjustable frequencies and
tolerance (on battery power)
60 Hz ± 0.1 Hz
Voltage variation for 0 to
100% load step change
± 1%
Permissible overloads
150% for 1 minute, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N
for nonlinear load
< 2% Ph-to-Ph
Battery
Standard battery technology
Sealed lead-acid battery (gas-recombination)
Inverter
Active power (kW)
36
45
54
72
90
117
Heat losses in kW Heat
Heat losses in BTUs
2.71
9250
3.39
11560
4.06
13870
5.42
18500
5.74
19610
7.47
25490
Storage temperature range
-13°F to 103°F (-25°C to +45°C)
Relative humidity
20% to 95%
Maximum operating altitude
without derating
3281 ft (< 1000 m)
Operating temperature range
at Pn
32°F to 104°F (0°C to 40°C)