3.8
UPS Personalization
Access to the Personalization Functions
CAUTION
Personalization must be carried out with switches Q1 (8) and Q5N (11) open (OFF)
and switch Q4S (9) closed (ON).
Figure 3-8: UPS Personalization
Personalization Settings
Operating Mode
Frequency
Automatic Bypass
Transfer to bypass AC source
Enabled
Disabled – disabled when
limiting
Transfer to bypass with bypass AC source out of
tolerances
Enabled
Disabled
UPS output frequency
60 Hz
60Hz
Tolerance for bypass AC source
8 %
0.5 - 1 - 2 - 4 %
Synchronization speed with bypass AC source
2 Hz / s
1 Hz / s
Function
Factory setting
Options
UPS operating mode
NORMAL
UPS automatic start
Disabled
Enabled
Authorized number of starts
4
1 to 255
Delay before reset of number of executed
automatic starts
4 seconds
1 to 60 seconds
The password
To change the password, see the Settings menu.
1 - Press the menu key (36).
2 - Select "Settings", then "Personalization" using the
function keys (35) or .
3 - Confirm by pressing the function key (35) .
4 - Enter the password by successively selecting each icon
using the corresponding function key.
5 - Confirm by pressing the function key (35) .
6 - To save the personalization settings, confirm by
pressing the function key (35) .
is factory set.