Installation and user manual – APC MGE GALAXY 5000 40 130KVA User Manual
Page 27

Installation and User Manual
2.5
Auxiliary Interconnections Between UPSs in Parallel Configurations
Figure 2-7: Redundant Parallel Configuration (Maximum Two UPS)
Exchange-current interconnections (19):
Link connectors XMS02 and XMS03 on the
two UPS units.
CAN // interconnections (21):
Fit a blue plug on connector XMS06 on
UPS1. Link connector XMS07 on UPS1 to
connector XMS06 on UPS2. Fit a red plug
on connector XMS07 on UPS2.
Note: The supplied cables (33 ft) limit the
distance between the two UPS units to
approximately 20 ft.