4.0 Parameter Settings

Below tables show operating parameters programmable from keyboard. Only qualified users
should alter programming parameters. See below examples.

Parameter Settings

*

Factory settings in bold

** For systems with active Battery Monitor only
*** Do not leave system running in bypass mode (Static bypass) for extended periods of time, as

batteries are not recharged in bypass mode.

Parameter

Setting*

Comments

Bypass operation

YES,

NO

YES will switch the system into
bypass mode***

Language

GB, D, F, DK, S, SF, NL, PL, CZ,
E, P, SK, H

Languages of text in display

Autostart

YES,

NO

Automatic restart by utility return
(1 min. delay). Ensures quick
battery recharge.

Remote shutdown active

YES,

NO

Shutdown of UPS by remote
signal when in battery operation.
Saves battery energy.

Remote shutdown

HIGH

, LOW

Nature of remote shutdown
signal level

Remote shutdown time

0, 1,

2

, 3, 4, 5, 6, 7, 8, 9, 10 min.

Time delay on remote shutdown
of UPS

Battery capacity test

Initiates back-up time check.
Time measured from start until it
reaches low DC warning level
(See User Guide, section 6).

Battery monitor test **

Initiates checks of battery
condition by 25% discharging.

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test
in cyclic intervals.

Battery monitor reset**

Press the

and

key to

reset alarm
(flashing light).

Boost charge

YES, NO

YES results in boost charge (10
hours)

Autoboost charge

YES, NO

YES results in boost charge after
battery operation (10 hours).

Enter new date

YYMMDD

Set to local date

Enter new time

HHMMSS

Set to local time (24 hour clock)