beautypg.com

APC SILCON 60-80KW 208/480V UPS User Manual

Page 16

background image

16

User Guide APC Silcon 60-80kW 208V/480V UPS

990-4035

Stop/Start UPS and Operating the External Service Bypass

2.7

Isolating one UPS in a Parallel Configuration for Service/Maintenance

2.7.1 Isolating one UPS in a Parallel/Redundant System

In a redundant system one UPS may be isolated for service/maintenance without affecting
other parallel UPS(s).

2.7.2 Switching Back the UPS to Normal Rarallel/Redundant Operation

The UPS will automatically switch to normal operation and start load-sharing with the other
parallelled UPS(s).

Service

bypass

switch

Load

Utility

APC Silcon

UPS

APC Silcon

UPS

Action

1. Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated.

2. Switch off the system to be isolated for maintenence by pushing the red OFF button.

3. Disconnect output and utility by setting output switches (Q002) to position 0 and input

switch (Q001) to position 0. Disconnect battery by opening battery breaker.

Action

1. Set the input switch (Q001) and the output switch (Q002) to position 1.

2. Charge capacitors, connect battery, and start up the UPS as described in 2.4.1. Start UPS

(from complete power down).

WARNING!

The system will discharge built-in capacitors.
ALWAYS check with a multimeter that the terminals contain no dangerous voltage before
touching the system!