beautypg.com

Airstream PNEG-343 User Manual

Page 13

background image

13

DRYER CONTROL PANEL

SAFETY CIRCUIT SHUTDOWN MESSAGES

The air switch contacts have closed

prior to the fan starting, indicating a

freewheeling blade or improper set-

ting of the air switch. The message

will distinguish between fan 1 and 2.

GRAIN DISCHARGE

WARNING

The lid on the grain discharge box

has opened, indicating that grain is

not being taken away fast enough

at the discharge box.

L1 VOLTAGE LOST

BURNER 1, 2 OR 3 VAPOR

HIGH TEMPERATURE

An over temperature condition has oc-

curred in the right side (left and right as

viewed from behind the dryer) grain col-

umn causing the control to shut down

the dryer. This control is adjustable

from 80

°

to 220

°

F, and automatically

resets itself when cool.

The LP gas vapor temperature sensor

located in the gas pipe train downstream

from the vaporizer, has opened indicat-

ing that the vaporizor is running too hot

and must be readjusted. This sensor is

set at 200

°

F and automatically resets

itself when cool. The message will dis-

tinguish between burner 1 and 2.

The contacts in the air switch have

opened due to insufficient airflow for the

burner to operate. The message will dis-

tinguish between burner 1 and 2.

BURNER 1, 2 OR 3 SHUT-

DOWN LOSS OF AIRFLOW

AUXILIARY SAFETY

SHUTDOWN

A shutdown has occurred due to an

auxiliary installed safety feature.

FAN 1, 2 OR 3 FAILURE

NO AIRFLOW

Contacts in the air switch have opened

due to the fan not turning, or the air switch

may need adjustment. The message will

distinguish between fan 1 and 2.

METERING ROLL DRIVE

SYSTEM FAILURE

The metering roll drive system has

failed to turn. A broken chain or

jammed metering roll is a possibility.

RIGHT METERING ROLL

FAILURE

The right (as viewed from behind the

dryer) metering roll has stopped turn-

ing, or the sensor has been damaged.

The left circuit breaker located on

the input/output board of the Elec-

tronic Monitoring Control System

has tripped, or one of the hardware

timers has shut down the dryer.

LOWER ADJUSTABLE

GRAIN HIGH

TEMPERATURE

FAN 1, 2 OR 3 CANNOT

START CHECK AIR SWITCH

The dryer has run low on grain, and

the out of grain timer has timed out,

shutting the dryer down. The unload

auger will clean out the dryer if it is

in continuous flow operation.

The right circuit breaker on the input/

output board has tripped.

12 VOLT POWER

SUPPLY WARNING

One of the thermal overloads on ei-

ther the fan, load, unload or auxil-

iary motors has opened, indicating

an overcurrent condition. The over-

loads must be manually reset.

An over temperature condition has oc-

curred in the left side (left and right as

viewed from behind the dryer) grain col-

umn causing the control to shutdown the

dryer. This control is set at 210

°

F and

automatically resets itself when cool.

MOTOR OVERLOAD

The flame sensor has failed to de-

tect a burner flame indicating that the

burner has failed to light, there is a

problem with the flame sensing cir-

cuitry or the dryer is not getting

burner fuel. The message will dis-

tinguish between burner 1 and 2.

BURNER 1, 2 OR 3 WARNING

FLAME NOT DETECTED

LOWER FIXED GRAIN

HIGH TEMPERATURE

The left (as viewed from behind the

dryer) metering roll has stopped turn-

ing, or the sensor has been damaged.

LEFT METERING ROLL

FAILURE

PLENUM 1, 2 OR 3 HIGH

TEMPERATURE

An over temperature condition has

occurred inside the dryer plenum.

This control is a 300

°

F limit and au-

tomatically resets itself when cool.

The message will distinguish be-

tween plenum 1 and 2.

FAN 1, 2 OR 3 HOUSING

HIGH TEMPERATURE

The temperature high limit located

on the fan/burner housing has

opened, indicating an over tempera-

ture condition has occurred towards

the rear of the fan/heater housing.

This control is set at 200

°

F and must

be manually reset. The message will

distinguish between fan 1 and 2.

OUT OF GRAIN WARNING/

UNLOAD CLEANOUT