Zv30hsrss ge monogram, 30" wall-mounted hood – GE ZV30HSRSS User Manual
Page 2
Specification Created 6/10
130678
ZV30HSRSS
GE Monogram
®
30" Wall-Mounted Hood
Advanced Planning
Ductwork Planning for vented mode
• This vent hood is designed to be installed beneath a cabinet
or beneath a cabinet mounted to a soffit.
• This hood is designed for 8" round ducting. The 8" round
duct can transition to 3-1/4" x 10" or 3-1/4" x 12".
• Plan the route for venting exhaust to the outdoors
considering any transitions you may require.
• Use locally supplied ducting to vent horizontally through the
rear wall or vertically through the ceiling.
• Use the shortest and straightest duct route possible. For
satisfactory performance, duct run should not exceed 100'
equivalent length for any duct configurations.
• Refer to "Duct Fittings" chart to compute the maximum
permissible length for duct runs to the outdoors.
• Install a wall or roof cap with damper at the exterior
opening. Order the wall or roof cap and any transition
and length of duct needed in advance from a local
hardware store.
• Determine the exact location of the vent hood.
• Wall or ceiling duct must be projected out at least 1" for
duct connection.
WARNING:
To reduce the risk of fire, use only
metal ductwork.
• For better air flow results, use rigid metal ductwork.
POWER SUPPLY
IMPORTANT - (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST
BE PROPERLY GROUNDED.
Remove house fuse or open circuit breaker before beginning
installation.
Do not use an extension cord or adapter plug with this
appliance. Follow national electrical codes or prevailing local
codes and ordinances.
Electric supply
These vent hoods must be supplied with 120V, 60Hz, and
connected to an individual, properly grounded branch circuit,
and protected by a 15 or 20 amp circuit breaker or time
delay fuse.
• Wiring must be 2 wire with ground.
• If the electrical supply does not meet the above
requirements, call a licensed electrician before proceeding.
• Route house wiring as close to the installation location
as possible. Wiring can enter from the ceiling or rear wall.
Route additional length from the ceiling or wall to reach the
junction box.
• Connect the wiring to the house wiring in accordance with
local codes.
Grounding instructions
The grounding conductor must be connected to a ground
metal, permanent wiring system, or an equipment-grounded
terminal or lead on the hood.
WARNING:
The improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative if
you are in doubt whether the appliance is properly grounded.
Ductwork Planning for recirculation mode
All parts are included to install in recirculation mode.
Mounting for adequate support
• The hood must be secured to vertical studs in the wall.
See the Wall or Ceiling and Cabinet Preparation section for
vented or recirculation installation.
• We strongly recommend that the vent hood be on-site to
accurately locate the ductwork and electrical service.
• Installation will be easier if the vent hood is installed before
the cooktop and countertop are installed.
IMPORTANT: The vent hood must be secured to the cabinet
and at least two wall studs and dry wall with anchors. The
cabinet must be capable of supporting 100 lbs.
For answers to your Monogram,
®
GE Profile
™
or GE
®
appliance questions, visit our website
at geappliances.com or call GE Answer Center
®
service, 800.626.2000.
Listed by
Underwriters
Laboratories