beautypg.com

Installation instructions, Warning, Caution – GE DCVH480EKWW User Manual

Page 19

background image

Installation Instructions

19

WARNING

USE ONLY METAL DUCT 4” DIAMETER (102 mm

FOR CANADA). DO NOT USE DUCT LONGER THAN

SPECIFIED IN THE EXHAUST LENGTH TABLE.

'U\HU([KDXVWLQJ,QIRUPDWLRQ³0HWDO'XFW2QO\
Ducting Materials:
For best performance, this dryer

should be vented with 4” diameter all-rigid metal

exhaust duct.
Exhaust Length Calculation:
1. Determine the number of 90º turns needed for

your installation.

2. The maximum length of 4’ rigid (aluminum or

galvanized) duct which can be tolerated is shown

in the table.

A turn of 45º or less may be ignored. Two 45º

turns within the duct length should be treated

as a 90º elbow.

A turn over 45º should be treated as a 90º elbow.

CAUTION:

For personal safety, do not

terminate exhaust into a chimney, under any

enclosed house floor (crawl space), or into an attic,

since the accumulated lint could create a fire hazard

or moisture could cause damage. Never terminate

the exhaust into a common duct or plenum with a

kitchen exhaust, since the combination of lint and

grease could create a fire hazard.

Exhaust ducts should be terminated in a dampered

wall cap to prevent back drafts, bird nesting, etc.

The wall cap must also be located at least 12” above

the ground or any other obstruction with

the opening pointed down.
Other terminations, such as louvered wall boxes,

are acceptable provided they are equivalent to

a 4” opening dampered wall cap.
For more information on venting kits and

accessories, please call 1.800.GE.CARES.

Best

Performance

Maximum

Length

of a 4

Dia.

Rigid Metal Duct

Exhaust Hood Type

Number of

A

B

90º

Turns

4

Opening

2-1/2

Opening

Front-Loading Dryers

0

90 ft.

60 ft.

1

60 ft.

45 ft.

2

45 ft.

35 ft.

3

35 ft.

25 ft.

4”

4”

2-1/2”