Alto-Shaam Platinum Series ASC-4G User Manual
Page 6

Gas Convection Oven - Electronic Control
Pg. 5.
G A S
S U P P L Y
&
I N S T A L L A T I O N
INSTALLATION REQUIREMENTS
GAS CONNECTION
:
3/4" NPT
CHECK PLUMBING CODES FOR PROPER SUPPLY LINE SIZING
TO ATTAIN BURNER MANIFOLD
NOTE:
If a flexible gas
line is used, it must be AGA approved, commercial
type and at least 1" I.D.
G A S P R E S S U R E C H A R T
The gas valve and burner have been fitted
according to the gas type specified on the
identification name plate.
TECHNICAL SPECIFICATIONS
N a t u r a l G a s
Min. connected pressure
7.0" W.C.
1.74 kPa
Max. connected pressure
14.0" W.C.
3.48 kPa
Orifice Size
#26
Manifold pressure
5.0" W.C.
1.25 kPa
Gross thermal output
50,000 Btu/hr
P ro p a n e G a s
Min. connected pressure
11.0" W.C.
2.74 kPa
Max. connected pressure
14.0" W.C.
3.48 kPa
Orifice Size
#43
Manifold pressure
10.0" W.C.
2.49 kPa
Gross thermal output
50,000 Btu/hr
G A S S P E C I F I C AT I O N S
FIELD CONVERSION OF FUEL TYPE
To convert from either fuel type, replace the orifice
located at the burner inlet with the desired orifice.
Set the manifold pressure to the corresponding
values located in the following table. The pressure
tap is located at either the lower elbow of the gas
train, below the main
ON
/
OFF
valve or in the pipe
near the regulator.
F U E L T Y P E
O R I F I C E S I Z E
O R I F I C E P
/
N
M A N I F O L D P R E S S U R E
Natural
# 26
OR-26431
5.0 IN/WC
Propane
# 43
OR-26430
10.0 IN/WC
D A N G E R
CONNECTING TO THE WRONG GAS
SUPPLY COULD RESULT IN FIRE OR
AN EXPLOSION CAUSING SEVERE
INJURY AND PROPERTY DAMAGE.
W A R N I N G
TO AVOID SERIOUS PERSONAL
INJURY, installation of this appliance
must conform to local, state, and
national codes; the current edition of
the American National Standard
Z223.1, National Fuel Gas Code, and
all local municipal building codes. In
Canada, installation must be in
accordance with Standard CAN/CSA
B 149.1 and Installation Codes - Gas
Burning Appliances, and local codes.