21

FAULT

POSSIBLE CAUSES

REMEDY

1) Mains cold water

Check and open Isolating

supply shut off

and/or stop valve. Check

water, Local Water Authority

NO HOT WATER

2) Line strainer

Turn off mains water supply,

FLOW

blocked

remove line strainer and
clean

3) Cold Water

Check direction of flow

Combination valve

arrows on valve, refit in

fitted incorrectly

correct position if necessary

1) Low mains water

Check pressure, consult

pressure

Local Water Authority if
necessary

REDUCED FLOW

2) Line strainer

Turn off mains water supply,

RATE

partially blocked

remove line strainer and
clean

3) Size of service

Increase to size stated on

pipe too small

page 6

1) Direct immersion

Check immersion heater,

heater is not

switch on if necessary

switched on

2) Direct thermal

Test thermostat operation

cut-out has

and wiring, if faulty,

operated

correct/replace. Reset cut-out

WATER FROM

3) Boiler programmer

Check switch on domestic

HOT TAPS

set to central

hot water if necessary

IS COLD

heating only
(Indirect models)

4) Boiler is not

Check boiler operation, if

functioning

fault suspected consult

(Indirect models)

manufacturer's instructions

5) Indirect thermal

Test thermostat operation

cut-out has

and wiring, if faulty,

operated

correct/replace. Reset
cut-out

6) Motorised valve

Check wiring and operation of

jammed or not

motorised valve correct/

wired correctly

replace as necessary

(Indirect models)

DISCHARGE FROM

1) Pressure above 7

Shut down boiler or immersion

PRESSURE/

bar, failure of

heater. Check pressure

TEMPERATURE

pressure reducing

reducing valve and thermal

RELIEF VALVE

valve. Temperature

controls. Replace if

above 90 C failure

necessary

of thermal control

DISCHARGE FROM

1) Continually.

Check pressure from valve.

EXPANSION

Pressure reducing

Replace if over 3.5 bar

VALVE

valve faulty

2) When heater is heating.

Check charge of vessel. Re-

Faulty expansion

charge vessel to 3.5 bar or

vessel or lost charge

replace if necessary