23

Product Specifications

Physical

Dimensions
(H × W × D)

Unit

Shipping

2.54 Ч 9.53 Ч 6.05 cm (1.00 Ч 3.75Ч 2.38 in)

7.26 Ч 24.13 Ч 16.51 cm (2.86 Ч 9.50 Ч 6.50 in)

Weight

Unit

Shipping

0.23 kg (0.50 lb)

0.36 kg (0.80 lb)

Distance (cable
length) between the
remote switch and
the RPO

3 m, normal; 60 m, maximum
(10 ft, normal; 200 ft, maximum)

Maximum number
of cascading units

10

Electrical

Power required

24 VDC at 35 mA, powered by the UPS port

Environmental

Temperature

Operating

Storage

0° to 45° C (32° to 113° F)

–15° to 65° C (5° to 149° F)

Relative Humidity

Operating

Storage

0 – 95%

0 – 95% non-condensing

Elevation

Operating

Storage

0 – 3000 m (0 – 10 000 ft)

0 – 15 000 m (0 – 50 000 ft)

Approvals

CE, EN 55024, EN 55082