40 control setting mode (set4) – TOHO ELECTRONICS TTM200 User Manual
Page 40

40
Control setting mode (set4)
toho
modbus
Screen
character
Name
Command Remark
Identifier
Absolute
(DEC)
Relative (hex)
BNK
41025
0400
bANK Switch to another bank
RWLB
BKH
41139
0472
bANKH Bank upper limit setting
RWLB
Pay attention to MODBUS
address.
SV1
41027
0402
SV Control set
RWLB
SLH
41029
0404
SLH SV limiter upper limit
RWLB
SLL
41031
0406
SLL SV limiter lower limit
RWLB
□MD
41033
0408
Md Control mode
RWLB
00000:RUN
00001:MAN
00002:RdY
00003:TIME1
00004:TIME2
00005:TIME3
CNT
41035
040A
CNt Set a control type
RWLB
TYP
41037
040C
tYP Set a PID control type
RWLB
BMD
41039
040E
bMd Set type B mode
RWLB
DIR
41041
0410
dIR Set a forward/backward action
RWLB
MV1
41043
0412
MV1 Main control operation amount
RWLB
M1G
41045
0414
MV1G Set an output gain
RWLB
TUN
41047
0416
tUN Set a tuning type
RWLB
ATG
41049
0418
AtG Set an AT factor
RWLB
ATC
41051
041A
AtC Set an AT sensitivity
RWLB
□AT
41053
041C
At Start/stop tuning
RWLB
00000: Stop
00001: Start
□P1
41055
041E
P1 Set a main control proportional band
RWLB
□I1
41057
0420
I Set an integration time
RWLB
□D1
41059
0422
d Set a derivative time
RWLB
□T1
41061
0424
t1 Set a main control proportional period
RWLB
ARW
41063
0426
ARW Anti-reset windup
RWLB
MH1
41065
0428
MLH1
Main control operation amount limiter, upper
limit
RWLB
ML1
41067
042A
MLL1
Main control operation amount limiter, lower
limit
RWLB
OU1
41069
042C
oU1 Set a main control change limiter rise
RWLB
OD1
41071
042E
od1 Set a main control change limiter decline
RWLB
SFM
41119
045E
SFM Set a main control soft-start output
RWLB
Pay attention to MODBUS
address.
SFT
41121
0460
SFt Set a main control soft-start time
RWLB
Pay attention to MODBUS
address.
FA1
41073
0430
FAL1 Set a main control anomaly
RWLB
1TS
41127
0466
tS1
Set a main control loop anomaly PV
threshold
RWLB
Pay attention to MODBUS
address.
1MS
41129
0468
MS1
Set a main control loop anomaly MV
threshold
RWLB
Pay attention to MODBUS
address.
1PS
41131
046A
PS1
Set a main control loop anomaly PV change
threshold
RWLB
Pay attention to MODBUS
address.
LP1
41075
0432
LoP1 Set a main control loop anomaly time
RWLB
CMD
41077
0434
CMod Set an OFF point position selection
RWLB
□C1
41079
0436
C1 Set a main control sensitivity
RWLB
CP1
41081
0438
CP1 Set an OFF point position
RWLB
FD1
41123
0462
Fdt1 Main control protection off timer
RWLB
Pay attention to MODBUS
address.
ND1
41141
0474
Ndt1 Main control protection on timer
RWLB
Pay attention to MODBUS
address.
MV2
41083
043A
MV2 Auxiliary control operation amount
RWLB
M2G
41085
043C
MV2G Set an auxiliary control output gain
RWLB
□P2
41087
043E
P2 Set an auxiliary control proportional band
RWLB
□T2
41089
0440
t2 Set an auxiliary control proportional period
RWLB
MH2
41091
0442
MLH2
Auxiliary control operation amount limiter,
upper limit
RWLB
ML2
41093
0444
MLL2
Auxiliary control operation amount limiter,
lower limit
RWLB
OU2
41095
0446
oU2 Set an auxiliary control change limiter rise
RWLB
OD2
41097
0448
od2
Set an auxiliary control change limiter
decline
RWLB