beautypg.com

Timeguard TRT044 User Manual

Page 4

background image

5. Specifications

Current rating:

16 (4) A

Voltage:

230V, 50HZ

Switch type:

Single pole, double throw

(SPDT)

Operating
temperature range: 0°C to 55°C

Set temperature
range:

40°C to 80°C

Complies with:

BS EN 60730

Conforms to
directives:

Conforms to

latest directives

Always isolate the mains supply before

starting work.
Incoming cable should be 1.5mm sq.
Remove cover from unit by unscrewing cover
retaining screw, and easing off the temperature

adjusting knob.
Thread incoming wire though the cable gland.
Allow sufficient excess cable to wire up the

unit, but not too much to make it difficult to
close the cover on the unit.
Connect the conductors to the relevant

terminals, according to the wiring diagram.
Ensure that the brass washer grips the conductor.
Pull some of the excess cable back through the

gland and then tighten the gland to trap the
cable and give good strain relief.
Replace the cover and the adjustment knob.
Adjust the length of the spring wire, and use it
to strap the TRT044 to the hot water cylinder.
Restore mains to the unit after checking all

system wiring is complete.

Cylinder/Pipe

Thermostat

Cat. No. TRT044

Operating & Installation Instructions

2. Siting

The TRT044 is designed to be surface mounted

onto the domestic hot water cylinder. For
cylinders with an insulating foam covering, a
section of foam must be removed so the back

of the thermostat is in direct contact with the
metal body of the tank.
The TRT044 should be mounted between a
quarter and third of the way up from the base

of the tank in a position that gives good access
to the dial.

3. Installation

This product should be installed by a qualified
installer to current installation standards.

If in any doubt contact the Timeguard Helpline

020 8450 0515.

Contents

TRT044 cylinder thermostat
TRT044 instruction leaflet

Spring wire
Wire strap

4. Operation

Use adjuster dial to set desired temperature.

For vulnerable people it may be advisable to

reduce the setting to as low as 50ºC bearing in
mind the outlet water temperature will be
somewhat higher than this due to the
temperature stratification in the tank.

To clean use a clean dry cloth only. Do not use

any liquid cleaners.

C 1 2

TRT044

Cylinderstat

Fig. 2

Wiring Diagram

Terminals C and 2 make on temperature rise.

Terminals C and 1 make on temperature fall.

Note:

Check boiler

instructions

before

connecting.

For a product brochure please contact:

Timeguard Ltd. Victory Park, 400 Edgware Road,

London NW2 6ND Tel: 020 8452 1112

or email [email protected]

A Group company

67-058-330 (issue 2)

HELPLINE

020 8450 0515

or email [email protected]

For assistance with the product please contact:-

3 Year Guarantee

In the unlikely event of this product becoming

faulty due to defective material or manufacture

within 3 years of the date of purchase, please

return it to your supplier in the first year with proof

of purchase and it will be replaced free of charge.

For years 2 and 3 or any difficulty in the first year

telephone the helpline on

020 8450 0515.

Note: a proof of purchase is required

in all cases. For all eligible replacements (where agreed by

Timeguard Ltd) the customer is responsible for all shipping/

postage charges for sending replacements outside the UK.

All shipping costs are to be paid in advance before

a replacement is sent.