Chapter 3: Installation

17 of 42

Chapter 3: Installation

3-1 Installation Location Considerations

Economical Series systems are portable and can be installed almost anywhere. As with all
equipment installations, follow all applicable codes and regulations.

The recommended ambient temperature range for Economical Series
installations is from +14ºF (-10ºC) to a maximum operating ambient
temperature of 131°F (55ºC). Recommended ambient storage temperature range

is from -13ºF to 149ºF (-25ºC to 65ºC). If storing the unit below freezing
temperatures, make sure the unit has an antifreeze mixture circulated inside.

Provide a minimum of twelve inches (12” or about 30 cm) clearance on all sides
of the cabinet to allow circulation of cooling air.

Locate the unit as close to the process as is practical.

3-2 Process Approach Temperature Considerations

If the differential (r) between COOLING WATER IN and TO PROCESS temperatures is less
than 10°F (7ºC), consult our Sales Department for advice on how to control low approach

applications.

3-3 External Piping Sizing Considerations

All external hose and piping should be adequately sized to assure minimum external pressure

drop.

Low external piping pressure drop is needed for best operation.

• Use a backup wrench to support Economical Series system piping when making process

piping connections.

All external valves, fittings, and hoses must be rated at a minimum of

150 psig and 250ºF (1,034.25 kPa/10.34 bars and 121ºC).

The exception is when the temperature control unit

is optionally rated for 300ºF (149ºC) operation;

external valves fittings and hoses must then be rated at a minimum of

150 psig and 300ºF (1,034.25 kPa/10.34 bars and 121ºC).