Cabinet Series Dehumidifying Dryer
43
2. Make sure jumper setting for input type is set for thermocouple TC-PT, middle jumper.
3. Return controller to housing.
4. Press the Display button for one (1) second to enter Menu Display.
5. Press the Up Arrow button to get to Setup mode.
6. To switch parameters within Setup mode, press the Display button.
Figure 8:
Setting List for Process Temperature Controller, Part No. A0548565
Mode Parameter
Setting
range Default
Factory
setting
Protect SECr Security
0 to 6
1
5
Protect YEYP A/M Key Protect
ON/OFF
OFF
ON
Manual Manual MV
-5.0 to 105.0%
0.0
Default
Mode Parameter
Setting
range
Default
Factory
setting
Level 0 SP Set Point
SP Lower Limit to Upper Limit EU
0
Default
Level 0 r-S Run/Stop
Run/Stop
Run
Default
Level 1 SP-0 Set Point 0
SP Lower to Upper EU
0
Default
Level 1 SP-1 Set Point 1
SP Lower to Upper EU
0
Default
Level 1 AL-1 Alarm Value 1
-1999 to 9999 EU
0
25.0
Level 1 AL-2 Alarm Value 2
-1999 to 9999 EU
0
25.0
Level 1 AL-3 Alarm Value 3
-1999 to 9999 EU
0
Default
Level 1 P Proportional Band
0.1 to 999.9% FS
10.0
4.4
Level 1 I Integral Time
0 to 3999 SEC
233
84
Level 1 d Derivative Timer
0 to 3999 SEC
40
13
Level 1 C-SC Cooling
Coefficient
0.01 to 99.99
1.00
Default
Level 1 C-db Dead Band
-19.99 to 99.99%FS
0.00
Default
Level 1 6F-r Manual Reset
Value
0.0 to 100.0%
50.0
Default
Level 1 HYS Hysteresis (Heat)
0.01 to 99.99%FS
0.10
Default
Level 1 CHYS Hysteresis (Cool) 0.01 to 99.99%FS
0.10
Default
Level 1 CP Control Period
(Heat)
1 to 99 SEC
20
Default
Level 1 C-CP Control Period
(Cool)
1 to 99 SEC
20
Default
Mode Parameter
Setting
range
Default
Factory
setting
Level 0 SP Set Point
SP Lower Limit to Upper Limit EU
0
Default
Level 0 r-S Run/Stop
Run/Stop
Run
Default
Level 1 SP-0 Set Point 0
SP Lower to Upper EU
0
Default
Level 1 SP-1 Set Point 1
SP Lower to Upper EU
0
Default
Level 1 AL-1 Alarm Value 1
-1999 to 9999 EU
0
25.0