PEP Filters HMF2 User Manual
Page 10
![background image](/manuals/373129/10/background.png)
HMF2 Series Filter System
Operating & Maintenance Manual
PEP Filters
• 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 •
www.pepfilters.com
10 of 19
Rev. 041204
For manual control units using a backwash water source other than the system:
1. Shut off the electrical power to the pump motor.
2. Move the handle on the linkage to position the valves in backwash mode.
3. Allow the filter to backwash for approximately two minutes.
4. Move the handle on the linkage to position the valves in the filtration mode.
5. Re-start the pump motor.
For manual control units using the system water for backwash:
1. Shut off the electrical power to the pump motor.
2. Move the handle on the linkage to position the valves in the backwash mode.
3. Re-start the pump motor.
4. Allow the filter to backwash for approximately two minutes.
5. Shut off the electrical power to the pump motor.
6. Move the handle on the linkage to position the vales in filtration mode.
7. Re-start the pump motor.
Filter Tank
The filter tank internal components should be visually inspected annually or
whenever back washing does not reduce the pressure of the filter tank to the
starting media gauge pressure. On HMF2 filters, remove the access port on top of
the tank to inspect internal components.
Note: Always use care and follow proper shutdown procedures. Inspect the over
drain assembly for any debris blockage or damage and clean or replace if necessary.
Remove and inspect the media. HMF2 filters have hand access ports located on the
side of the tank for easy media removal under drain inspection. Over a period of
time, foreign matter may become embedded in the media pack that will not back
wash. Contaminated media should be discarded. Unscrew the under drain laterals
and inspect for blockage or damage. Clean or replace if necessary. Refill tank with
the proper amount of new media, following the media loading instructions found in
Table 6.