Code Configuration

Pressure unit

Pressure unit

Pressure unit

Pressure unit

Pressure unit

5

MPa(7-70bar)

6

Pa(25mbar-7bar)

7

kPa

8

bar

9

mH2O(with 70bar,

otherwise mmH2O)

10

mmHg(not with

70bar)

11 psi

12

inH2O

13

inHg (not with

70bar)

14

hPa

15

mbar

Resolution

Resolution

Resolution

Resolution

Resolution

0

low

1

high

Damping

Damping

Damping

Damping

Damping

0

on

1

off

Baudrate

Baudrate

Baudrate

Baudrate

Baudrate

0

1200 Baud

1

2400 Baud

2

4800 Baud

3

9600 Baud

Code Configuration

Switch. off time

Switch. off time

Switch. off time

Switch. off time

Switch. off time

0

60 min

1

continous

2

1 min

3

10 min

Time unit

Time unit

Time unit

Time unit

Time unit

0

/hours

1

/minutes

Storage interval

Storage interval

Storage interval

Storage interval

Storage interval

2

10 s

3

20 s

4

30 s

5

60 s

6

2 min

7

3 min

8

5 min

9

10 min

10

30 min

11

60 min

12

manual

13

off

14

1 s

15

5 s

Display rate

Display rate

Display rate

Display rate

Display rate

0

5 Hz

1

2.5 Hz

Reply to control command

«

readconfig

»

A whole number is returned as a reply

msb

lsb

#### #### #### ####

|||| |||| |||| ****-

Pressure unit

|||| |||| |||*------

Resolution

|||| |||| ||*-------

Damping

|||| |||| **-------- Baudrate

|||| ||**-----------

Switching off time

|||| |*-------------

Time unit

|***-*--------------

Storage interval

*-------------------

Display rate

3.5

RS 232 mode

The HM28 can be remotely operated from a
personal computer via an RS 232 interface.
The automatic switching off (chapter 3.1) is
inactive. Connection by means of a RS232-
cable.

Plug pin assignment RS 232, DB 9 (female)

Pin

Assignment

Pin

Assignment

1

DCD

6

DSR

2

TXD

7

RTS

3

RXD

8

CTS

4

DTR

9

SHIELD

5

GND

Protocol
ASCII-commands
9600/4800/2400/1200 baud, 8 bit, no parity,
1 stop bit,
XON/XOFF - protocol (17 dec/19 dec)

Notes

- The HM28 is switched on when the

supply voltage is applied

- The HM28 sends "XON" every 3 seconds

To determine the baud rate, read-in

"XON" in each transfer rate until "XON"

is correctly identified

- To go to remote control mode, interrogate

"XON", immediately send the "remote"

command and then read-in the

acknowledgement "ok"

- Only lower case letters are accepted

- Observe > 0,1 s delay before the next

command after "setbaud" command

- To acknowledge the answer of the HM28

without reading it back, just send a "XON"

- The symbol "*" followed by the checksum

must be suffixed to each string. The string

must be terminated with a CR

- A "TAB" is prefixed to each answer of the

HM28, a "*" suffixed and the checksum

sent.

The answer is terminated with a CR

- The checksum is formed from the least

significant byte of the command string

Code-decoding of control command

«

readconfig

»