beautypg.com

C-1100v, Circuit board connections, Page 7 – Blue-White C-1100 CHEM-FEED Diaphragm Pump User Manual

Page 7: Open collector motor on output schematics, Typical example output schematic

background image

C-1100V

Page 7

CIRCUIT BOARD CONNECTIONS

AC sine waves

Jumper Not Installed

(open - factory default)

Digital square waves

Jumper Installed

DC

MOTOR

BLACK (-)

RED (+)

Ground (green)

Earth Ground (green)

Common

Hot

AC

Input

Power

PROTECTOR FUSE

1 Amp, 250 Volt AC

(Littlefuse #239001

or Equivalent)

1 AMP

250VAC

MOTOR

RED (+)

MOTOR

BLACK (-)

AC LINE

NEUTRAL

AC LINE

HOT

TS

THERMAL SWITCH

.187 push tab connectors

2 conductors

110

110

220

AC LINE VOLTAGE SETTINGS

230 VAC

One Jumper Installed

on center position

(ends open)

115 VAC

Two Jumpers Installed

on end positions

(no open pins)

INPUT SIGNAL CONNECTOR

7 wire bundle

Hz INPUT JUMPER SETTINGS

Located under connector

PROBE

NC

NO

ALARM OUTPUT

(CONTACT CLOSURE)

normally open (NO)

(factory default)

TUBE FAILURE SENSOR

PROBE INPUT

2 Grey wires pump head sensors.

BLUE (4-20 mA input)

BLACK (Ground)

YELLOW (verification sensor input)

ORANGE (0-10 VDC input)

RED (+20VDC)

WHITE (frequency input)

JUNCTION BOX

LIQUID-TIGHT
CONNECTOR

ACCEPTABLE CABLE JACKET RANGE:

.118 - .255 INCH
.( 3,0 - 6,5 MM)

EXTERNAL INPUT CABLE

BROWN (motor-on contact output)

PURPLE X2 (alarm relay contacts)

OPEN COLLECTOR MOTOR ON OUTPUT SCHEMATICS

(+) 6 to 30 Vdc

MA

(-) DC Ground

(+) Vdc

(-) Vdc

MAX
LOAD
50mA

2K ohm resistor typical

(+)
24Vdc

(-) 24Vdc

2K ohm

Relay
50mA max coil

TYPICAL EXAMPLE

OUTPUT SCHEMATIC

BROWN (+)

BLACK (-)