Manual 05615 Rev. D
Page 3
VENTING DEVICE
(Standard on all Stationary Extinguishes, Optional on Wheeled Extinguishers)
A venting device has been installed on all stationary extinguishers to provide a means of safely and easily
relieving residual nitrogen pressure from the agent cylinder while utilizing the same pressure to evacuate or "blow
down" the hose.
INSPECTING THE EXTINGUISHER
This extinguisher should be inspected at regular intervals (monthly or more often if circumstances
dictate) to insure that it is ready for use. Inspection is a "quick check" that a fire extinguisher is available
and is in operating condition. It is intended to give reasonable assurance that the fire extinguisher is fully
charged. This is done by verifying that it is in its designated place, that it has not been actuated or
tampered with, and that there is no obvious physical damage or condition to prevent its operation.
THE FFFP FOAM CHARGE IN THIS EXTINGUISHER MUST BE REPLACED EVERY THREE YEARS PER
NFPA 10. USE ONLY THE AMEREX MODEL 534 CHARGE. USE OF ANY OTHER AGENTS OR
SUBSTITUTES WILL VOID THE UL LISTING AND AMEREX WARRANTY. SEE THE RECHARGE SECTION
OF THIS MANUAL FOR THE APPROPRIATE EMPTYING AND RECHARGING INSTRUCTIONS.
AMEREX CORPORATION DOES NOT SERVICE, MAINTAIN OR RECHARGE FIRE EXTINGUISHERS. THIS
MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION,
MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY. NO INSTRUCTION MANUAL CAN
ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE ENCOUNTERED IN THE SERVICE OF FIRE
EXTINGUISHERS. DUE TO THE POSSIBILITY THAT PRIOR SERVICE PERFORMED ON THIS EQUIPMENT MAY
HAVE BEEN IMPROPERLY DONE, IT IS EXTREMELY IMPORTANT THAT ALL WARNINGS, CAUTIONS AND
NOTES IN THIS MANUAL BE CAREFULLY OBSERVED. FAILURE TO HEED THESE INSTRUCTIONS COULD
RESULT IN SERIOUS INJURY.
AMEREX ASSUMES NO LIABILITY FOR SERVICE, MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY
PUBLISHING THIS MANUAL.
OPERATION
– After the fire has been successfully
extinguished and it has been determined that it is
completely out:
1. Confirm that the nozzle lever is in the CLOSED
position.
2. Close the nitrogen valve (move "T" handle to
CLOSED position)
3. Remove ring pin and CLOSE agent cylinder valve
(Valve A in Fig. 1) to prevent further chemical from
entering the hose.
4. Remove ring pin and OPEN pressure vent valve
(Valve B in Fig. 1) to allow nitrogen gas to by-pass
the chemical and pressurize the hose.
5. Open discharge nozzle to vent all residual chemical
and nitrogen gas pressure.
6. Re-open nitrogen valve if additional pressure is
required.
7. When recharging this unit, reset agent cylinder and
vent valves, install ring pins and lockwire seals.
CAUTION:VALVE SHUT-OFF HANDLES MUST
BE
IN
THE
POSITIONS
SHOWN
WHEN
EXTINGUISHER IS ON STANDBY OR IN
ACTUAL OPERATION.