Ultima compact condensing units, Installation data, Condensers & condensing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual
Page 24: Electrical data

ULTIMA COMPACT
Condensing Units
24
Condensers & Condensing Units
Installation & Maintenance : 6259675 IM V1.4.0 10/2013
Installation Data
ELECTRICAL DATA
UCCU270D-8/2
UCCU300D-8/2
UCCU330D-10/2
UCCU360D-10/2
UCCU400D-12/2
UCCU450D-12/2
Unit Data
Nominal Run Amps
(1) A
188
206
231
252
279
303
Maximum Start Amps
(2) A
337
389
462
483
552
576
Permanent Supply
VAC
230 V 1 PH 50 Hz
Mains Supply
VAC
400 V 3 PH 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
16
Rec Mains Fuse Size
A
200
250
250
315
315
355
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Control Circuit
VAC
24V/230V AC
Condenser Fan - Per Fan
Full Load Amps
A
1.75
1.75
1.75
1.75
1.75
1.75
Locked Rotor Amps
A
6.20
6.20
6.20
6.20
6.20
6.20
Motor Rating
kW
0.98
0.98
0.98
0.98
0.98
0.98
Compressor - Per Compressor
Quantity
3 + 3
6
3 + 3
6
3 + 3
6
Motor Rating
kW
15.0 / 11.7
15.0
18.2 / 15.0
18.2
22.8 / 18.2
22.8
Nominal Run Amps
(1) A
32.0 / 26.0
32.0
39.0 / 32.0
39.0
47.0 / 39.0
47.0
Crankcase Heater Rating
W
130.0 / 75.0
130.0
130.0 / 130.0
130.0
130.0 / 130.0
130.0
Start Amps
(2)
215.0 / 175.0
215.0
270.0 / 215.0
270.0
320.0 / 270.0
320.0
Type Of Start
Direct on line
QUIET DQ
UCCU270DQ-10/2 UCCU300DQ-10/2 UCCU330DQ-12/2 UCCU360DQ-12/2 UCCU400DQ-14/2 UCCU450DQ-14/2
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
1.15
1.15
1.15
1.15
1.15
1.15
Locked Rotor Amps
A
2.10
2.10
2.10
2.10
2.10
2.10
Motor Rating
kW
0.70
0.70
0.70
0.70
0.70
0.70
SUPER QUIET DSQ
UCCU270DSQ-12/2 UCCU300DSQ-12/2 UCCU330DSQ-14/2 UCCU360DSQ-14/2 UCCU400DSQ-16/2 UCCU450DSQ-16/2
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
0.83
0.83
0.83
0.83
0.83
0.83
Locked Rotor Amps
A
1.50
1.50
1.50
1.50
1.50
1.50
Motor Rating
kW
0.32
0.32
0.32
0.32
0.32
0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1) A
167
182
207
228
246
261
Maximum Start Amps
(2) A
337
389
362
483
552
576
Recommended Mains Fuse
A
200
200
250
250
250
315
Compressor Nominal Run Amps
- Per Compressor
A
3 x 24 / 3 x 20
6 x 24
3 x 30 / 3 x 24
6 x 30
3 x 36 / 3 x 30
6 x 36
Electronic Soft-start
Nominal Run Amps
(1) A
188
206
231
252
279
303
Maximum Start Amps
(2) A
267
303
354
375
424
448
Recommended Mains Fuse
A
200
250
250
315
315
355
(1)
Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.
(2)
Starting amps refers to the direct on line connections.