Condensing units cu 1 – 4, Capacity data - cooling only unit – Airedale Condensing Units (CU) 3kW - 80kW User Manual
Page 5

Condensing Units
CU 1
– 4
5
Condensing Units
5
Technical Manual : 904-020 v1.3.0 02_13
Capacity Data - Cooling Only Unit
Cooling
Duty
Mean
Evaporating
Temperature °C
Ambient
25°C
30°C
35°C
40°C
45°C
Output kW Input kW
Output kW Input kW
Output kW Input kW
Output kW Input kW
Output kW
Input kW
CU1
-5
2.62
0.90
2.45
1.04
2.30
1.19
2.13
1.33
1.96
1.47
0
3.11
0.95
2.92
1.08
2.73
1.23
2.55
1.37
2.35
1.51
5
3.70
0.98
3.50
1.12
3.30
1.26
3.10
1.41
2.90
1.55
10
4.32
1.02
4.11
1.15
3.90
1.28
3.67
1.44
3.44
1.59
CU1.5
-5
3.57
1.27
3.35
1.47
3.14
1.68
2.91
1.87
2.68
2.08
0
4.25
1.31
4.02
1.52
3.79
1.71
3.55
1.92
3.31
2.13
5
5.05
1.38
4.79
1.58
4.51
1.78
4.24
1.99
3.97
2.19
10
5.90
1.44
5.62
1.63
5.33
1.81
5.02
2.04
4.70
2.25
CUS2
-5
4.01
1.09
3.76
1.26
3.52
1.44
3.27
1.61
3.01
1.79
0
4.77
1.13
4.51
1.31
4.25
1.47
3.98
1.65
3.71
1.83
5
5.67
1.19
5.37
1.36
5.06
1.53
4.76
1.71
4.45
1.88
10
6.62
1.24
6.30
1.40
5.98
1.56
5.63
1.75
5.27
1.93
CUS2.5S
-5
5.97
1.74
5.61
2.01
5.24
2.26
4.83
2.55
4.41
2.83
0
7.12
1.82
6.73
2.08
6.34
2.34
5.90
2.63
5.46
2.91
5
8.40
1.93
7.98
2.18
7.55
2.42
7.06
2.72
6.56
3.01
10
9.80
2.03
9.32
2.27
8.84
2.51
8.26
2.80
7.68
3.08
CUS2.5T
-5
5.90
1.72
5.69
2.00
5.47
2.27
5.27
2.54
5.53
2.82
0
7.18
1.83
6.81
2.08
6.43
2.34
6.07
2.59
5.66
2.90
5
8.40
1.91
7.99
2.17
7.57
2.42
7.13
2.71
6.68
2.99
10
9.70
2.02
9.25
2.27
8.79
2.51
8.31
2.79
7.82
3.07
CUS3
-5
6.99
2.13
6.62
2.44
6.26
2.75
5.91
3.07
5.50
3.44
0
8.28
2.27
7.86
2.54
7.44
2.81
6.99
3.14
6.54
3.53
5
9.69
2.38
9.20
2.69
8.72
2.96
8.22
3.30
7.67
3.63
10
11.20
2.51
10.67
2.79
10.12
3.09
9.55
3.42
8.99
3.74
CUS3.5
-5
8.66
2.48
8.19
2.79
7.71
3.10
7.23
3.42
6.75
3.73
0
10.38
2.60
9.82
2.91
9.25
3.21
8.72
3.54
8.18
3.86
5
12.35
2.77
11.56
3.05
10.76
3.33
10.24
3.66
9.72
3.98
10
14.18
2.93
13.29
3.20
12.39
3.46
11.89
3.79
11.39
4.12
CUS4
-5
10.56
2.50
9.85
2.98
9.18
3.46
8.54
3.95
8.54
3.95
0
12.44
2.63
11.74
3.11
11.05
3.59
10.32
4.07
9.78
4.61
5
14.54
2.86
13.80
3.33
13.05
3.79
12.37
4.27
11.75
4.80
10
16.95
3.11
16.17
3.56
15.38
4.00
14.51
4.45
13.62
5.00
1
Output kW refers to the compressor duty.
2
Input kW refers to the compressor input power only.
3
Cooling data for a cooling only unit.