Accessories, On-off valves with thermoelectric actuator – Airedale Chilled Water Cassette 2kW - 11kW User Manual
Page 19
![background image](/manuals/370951/19/background.png)
20
Technical Manual:
6806236 0
/20
CHILLED WATER CASSETTE
Model
0.2/1.2/2.2/3.2
0.4/1.4/2.4/2.6/3.4/3.6
4.2/5.2/6.2
4.4/5.4/5.6/6.4/6.6
0.4/1.4/2.4/2.6/3.4/3.6
4.4/5.4/5.6/6.4/6.6
Battery
type
Main
Auxiliary
*
maximum pressure difference for valve to close
**
external thread. flat seal
2 way valves
3 way valves
K
vs
m
3
/h
3
¨p
max
kPa *
Valve **
connection
K
vs
m
3
/h
3
¨p
max
kPa *
Valve **
connection
2.8
5.2
2.8
50
60
50
3/4"
1"
3/4"
2.5
4.5
2.5
50
50
50
3/4"
1"
3/4"
Max. ambient temperature:
Max. water flow temperature:
Power:
Rating:
Protection:
Travel time:
Max. glycol content of water:
16 bar
50 °C
110 °C
230 V - 50/60 Hz
3 VA
IP 43
approx. 3 min.
50%
ON-OFF valves with thermoelectric actuator
Valve set, 2 or 3 ways, ON-OFF, with thermoelectric actuator.
The set includes connection pipes and holders.
Note: The main battery valve connection
is 1/2” (Kvs 2) for TL0 - TL1 - TL2 - TL3 sizes
and 3/4” (Kvs 3,5) for TL4 - TL5 - TL6 sizes,
the auxiliary battery valve connection is 1/2” (Kvs 2).
Note: The maximum pressure drop accross
the fully open valve should not exceed 25 kPa
for cooling operation and 15 kPa for heating operation.
Technical data:
Valves characteristics
Valves pressure drop
V
ALVE WITH
M
ICROMETRIC
L
OCKSHIELD
V
ALVE
(
WATTS INDUSTRIES
-
HONEYWELL
)
V
ALVE WITH
S
IMPLIFIED
K
IT
(
JCI
)
Accessories