Electronic controls, Identification code – Airedale Chilled Water Cassette 2kW - 11kW User Manual
Page 13
![background image](/manuals/370951/13/background.png)
14
Technical Manual:
6806236 0
/20
CHILLED WATER CASSETTE
Same characteristics as TMO-T, adding:
- Manual or automatic speed switch.
- Electronic thermostat for fan control (ON-OFF).
- Electronic thermostat for valve(s) control (ON-OFF).
- Simultaneus thermostatic control of the valves and fan (ON-OFF).
- It allows installation of the Summer/Winter switch centralised and remote, or to control it with an automatic change-over
fitted on the water pipe (for 2 pipe installations only)
Note: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/winter
change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Dead Zone 2°C).
LEGEND
SEC1 = Airedale electrical board
SET1 = Control electrical board
CH
= Remote Summer/Winter switch
SB
= Alarm contacts
E
= Valve set (2 pipe installation)
E1
= Hot water valve set
E2
= Chilled water valve set
AL
= Alarm condensate - float switch released
- Speed switch (slave).
- It allows to control up to 8 units with only one centralised thermostat
using one speed switch for each unit.
- For controls TMO-T and TMO-T-AU.
Electronic controls
Identification
Code
TMO - T - AU
9060520
Identification
Code
SEL - S
9079110