Technical Manual:
6806236 0
/20
CHILLED WATER CASSETTE
Identification
Code
CAP
6078005
Identification
Code
CH 15-25
9053049
Identification
Code
TME
3021091
m
3
/h
Pa
160
200
300
400
500
3
8
15
25
36
TL 4-5-6
m
3
/h
Pa
80
120
160
200
240
3
8
15
25
36
TL 0-1-2-3
Correlation between
flow-rate / static pressure
RED
BLACK
PRT 800
9079231
TL 4-5-6
Identification
Code
PRT 600
9079230
Model
TL 0-1-2-3
TME low temperature cut-out thermostat
Suitable for wall controls only (not infra-red remote control). To be fitted between the coil fins;
when connecting the control, the TME probe cable must be separated from the power supply wires.
To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI.
The fan stops when the water temperature is lower than 38°C
and it starts the fan when it is higher than 42°C.
Change-Over CH 15-25
Suitable for wall controls only (not for infra-red remote control).
Automatic summer/winter switch to be installed
in contact with the water circuit (for 2-tube installations only).
To be used with the following controls:
TMO-T, TMO-T-AU, TMO-DI.
Fresh air connection
See page 13.
Fresh air kit
This is used to introduce primary air into the environment directly through the
diffuser. The kit includes a flow separator to be fitted inside the cassette, and
a circular fitting for connection to the flexible system ducting. The flow of air is
sent directly to just one of the outlet louvers, without passing through the coil.
The air flow of fresh air introduced into the environment depend on the inlet
static pressure.
The diameter of the fitting
is 150 mm for TL 0 - 1 - 2 - 3
and 180 mm for TL 4 - 5 - 6.
Units with remote electric board
On request the Airedale cassettes are available with electric control panel reachable from below and with the electric
board that can be placed in a remote position. In this case the units are supplied with an electronic connecting control
panel, fitted to the bottom side on the 4 smallest sizes and to the
lateral side on the 3 biggest sizes.
The electronic control panel is connected to the fan motor, to the
condensate pump and to the condensate level control. A 6 m wire
is also supplied with integral plug-in connections to connect the unit
with the remote electric board that can be installed in a suitable and
comfortable position, where the power and system connections can
be made easily.
This feature is not available for units with electric resistance or infra-
red remote control.