Positioning, Water system, Chillers logicool – Airedale LogiCool FreeCool 40kW User Manual
Page 33: Installation data

Chillers
LOGICOOL
™
Chillers
33
Technical Manual : 6521355 V1.8.0 07/2014
Installation Data
POSITIONING
The installation position should be selected with the following points in mind:
Position on a stable and even base, levelled to ensure that the compressor
operates correctly
Levelling should be to +/- 5mm
Where vibration transmission to the building structure is possible, fit pad anti-
vibration mounts and flexible water connections
Observe airflow and maintenance clearances
Pipework and electrical connections are readily accessible
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
Within a side enclosed installation, the fan MUST be higher than the
enclosing structure
Multiply x 2 airflow clearance for 3 side enclosed applications
Ensure there are no obstructions directly above the fans
Allow free space above the fans to prevent air recirculation
CAUTION
Prior to connecting services, ensure that the equipment is installed and
completely level.
LEFT SIDE
FRO
NT
(2)
1000
(1)
(2)
1500
(1)
REA
R (CO
IL
)
(1) Airflow clearance minimum (mm),
multiply x 2 between units.
(2) Maintenance clearance minimum:
unit minimum 200mm
RIGHT SIDE
WATER SYSTEM
Chilled water pipework and ancillary components must be installed in accordance with:
National and Local Water supply company standards
The manufacturer's instructions are followed when fitting ancillary components
The system liquid is treated to prevent corrosion and algae forming
Glycol required as standard, with the correct concentration to suit the lowest ambient
the equipment will experience
The schematic is referred to as a guide to ancillary recommendations
CAUTION
The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.