Spectrex Series 200 Open-Path Gas Detection System User Manual
Page 38
Spectrex Inc. - SafEye
TM
200 Gas Detector Manual – TM 792100, Rev. D, May 2004
30
5.4.4 Detector / Source Installation (Figure No. 8 and 9)
1. Place the Tilt Mount holding plate (Item 1) in its designated location and
secure it with (4) fasteners through four (4) holes dia. 8.5mm.
2. Install the Detector Base Assy. (Item 2) on the Tilt Mount use cap socket
screw (Item 3) and Spring Washer (Item 4).
Notes:
1
Skip steps 1 and 2 if the Tilt Mount is already installed.
2
Detector removal for maintenance purpose does not require Tilt
Mount removal
3. Place the detector, with its conduit/cable inlets pointing downwards on the
detector base assy. of the Tilt Mount (Item 2). Secure the detector with
four 1/4”- 20 UNC - 3A x 1/2” screw with No. 1/4” spring washers to the Tilt
Mount. Use 1/4” Hex Key for 3/16” screw.
4. Repeat 1 - 2 to install the Source
5.5 Mounting for Duct Installation
The following instructions are applicable for both the Source unit and the
Detector unit.
The detector may be mounted on a special Duct Mount. The Duct Mount enables
the detector to be rotated up to ±3 degrees in the X-Y directions in order to
provide fine alignment.
For duct installation use Duct Mount P/N 794716.
The Duct Mount Kit supplied with the item listed in Table 18 as follows:
Table 18. Duct Mount Kit
Item
Qty
Duct Mount Set
1
Open & closed Wrench No. 10 key
1 per installation
Closed No. 10 Key
1 per installation
5.5.1 Duct Mount Set (Figure 11, 12)
The Duct Mount set consists of Fitting Plates, Sealing Rings, Windowed plate,
and securing elements combined with appropriate screws and nuts. It provides a
reliable attachment of the detector to the air intake as well as good sealing and
accurate alignment capability.