Spectrex Series 200 Open-Path Gas Detection System User Manual
Page 18
Spectrex Inc. - SafEye
TM
200 Gas Detector Manual – TM 792100, Rev. D, May 2004
10
Zero calibration must be done after installation, re-alignment and window
cleaning, using magnetic mode selection
3.5 Mode Selection
A Magnetic Mode Selector is used to change to alignment and calibration modes
by placing the magnet on the side of the detector (Figure 16).
3.6 Visual Indications LEDs
There are two indicators (LEDs) located in the detector’s front window, referred
to as the right and left LEDs. They display red, orange and green light that can
be either ‘On’ steady or flashing or ‘Off’
Table 2. LED Status Indication
Status
Remarks
Left LED
Right
LED
LED
Status
4-20mA
Output
Normal
Green
Off
On
4 mA
Warning
See Note 4
Red
Off
On
14 mA
Alarm
See Note 4
Red
Red
On
19 mA
Fault 1
Orange
Off
On
2 mA
Fault 2
Orange
Orange
On
0 mA
Low
Voltage
Orange
Orange
Both LEDs
flash at
rate of 2Hz
0 mA
First receives the
intensity compared
to the last
calibration: The
intensity is min.
80% of the last
calibration intensity
Green
Green
0 mA
80% - 60%
Orange
Green
0 mA
60% or less
Red
Orange
0 mA
Alignment
Mode
After 20 seconds
the color
represents the
signal intensity
(See Note 2).
See Note
1
See Note
1
0 mA
Standby
mode
Green
Green
Both LEDs
flash
alternately
at a rate of
2Hz.
0 mA
Calibration
mode
See Note 3
Off
Off
0 mA