beautypg.com

Spectrex Series 200 Open-Path Gas Detection System User Manual

Page 25

background image

Spectrex Inc. - SafEye

TM

200 Gas Detector Manual – TM 792100, Rev. D, May 2004

17

Notes:
1 Detection flash rate can be selected by pre-setting of SW1-1 and SW1-2

according to the following table. There are two bits, which provides four Flash
Source rates. Same Flash rate should also be set at the Flash Source.

Table 8. Flash Source Flash Rate Configuration

bit # 0 position

(SW1-1)

bit # 1 position

(SW1-2)

Source flash Rate

(flashes/second)

off

off

0.5

on

off

1

off

on

2

on

on

4

2 Four Gas types can be selected for maximum compatibility to Gas spectral

properties. The selection of the appropriate type is defined by pre-setting of
SW1-3 and SW1-4 according to the following table:

Table 9. Gas Type Calibration Setup

bit # 0 position

(SW1-3)

bit # 1 position

(SW1-4)

Detected Gas

Type

Gas type as

defined in

Section 2.3.6

off

off

Methane

Gas 1

on

off

Mixture

Gas 2

off

on

Propane

Gas 3

on

on

Mixture

Gas 4

Address Selection Switch

The Address selection Switch provides up to 64 different addresses for the
detector upon a network installation. Each detector can be recognized at its
specific address in RS485 network. The address should be determined by a pre-
setting of SW2-1 to SW2-6 switches.

Attention!

SW2-7 and SW2-8 should be always at on.