Dis con tin ued – Seametrics FT500 User Manual

Page 3

background image

Displays

Connections

GND
+12VDC

POWER SUPPLY INPUT

- (BLACK)
+ (RED)

GND (BLACK)
INPUT SIGNAL (WHITE)
+12VDC {RED}

}

}

}

TO FLOW METER

SCALED OUTPUT PULSE
TO METERING PUMP

N.O.

COMMON

N.C.

N.O.

COMMON

N.C.

K1 RELAY

LOW FLOW

ALARM

{

{

K2 RELAY

HIGH FLOW

ALARM

FOR REED SWITCH TYPE METERS
USE GND AND INPUT TERMINALS ONLY

CHART RECORDER -
CHART RECORDER +

CHART RECORDER -
CHART RECORDER +

0-10 VDC
OUTPUT

4-20mA
OUTPUT

NOTE: OUTPUT TYPE IS FACTORY SET
CONSULT FACTORY TO CHANGE

N.O.

COMMON

N.C.

N.O.

COMMON

N.C.

K1 RELAY

LOW FLOW

ALARM

{

{

{

{

{

K2 RELAY

HIGH FLOW

ALARM

110 VAC

INPUT

NEUTRAL

HOT

GND

GND
INPUT
+12 VDC

GND
+ OUTPUT

TO FLOW METER
FOR REED SWITCH TYPE METERS
USE INPUT AND GND TERMINALS ONLY

SCALED OUTPUT PULSE
TO METERING PUMP

Optional 12-18 VDC Power

Standard 110 VAC Power

Optional Analog Output

RATE

1234 GPM

TOTAL 12345678 GAL

RESETS TOTAL

AND UPDATES UNITS

UNITS = GALLONS/MIN

Dsply Contrast = 14

for 4-20ma change

K Factor

1.000

UPDATE TIME=1000ms

HI ALM

195 GPM

LO ALM

97 GPM

10 Gals. / Pulse

4mA

0 GPM

20mA

195 GPM

RUN

PROGRAM

for METER change

for UPDATE change

When in PROGRAM the “ ” and “ ”
keys add or subtract from the
value displayed

The 4-20ma display only appears if
the optional AC10 board is installed.

for OUTPUT change

TO RESET TOTAL

Note:

Note:

3 of 4