beautypg.com

Precision Control Systems 915 User Manual

Page 21

background image


Page 18 of 21

480 VAC units: 3,750 VDC
240 VAC units: 1,875 VDC
120 VAC units: 0.917 VDC
Adjust the EXT 200 span potentiometer if necessary.

7. Verify that the panel voltmeter reads the voltage as set in Step 5 above. If necessary,

carefully remove the front cover of the meter and adjust the span potentiometer for a +/-
1 reading.


Temperature Controller Option
Refer to the temperature controller manual for calibration instructions.

Line Voltage Re-Configuration


The AC line voltage for the Model 915 Power Control System may be re-configured. A wire
with wire number 1070 is connected to pins 2, 3, or 4. Move this wire to the pin corresponding
to the desired line voltage.

Pin 2

120 VAC

Pin 3

240 VAC

Pin 4

480 VAC