MODEL 1029C

18

10/19/2007

MODEL NUMBER IDENTIFICATION

1029C-[X]-[XXX]V-[XXX]A-IL[XXX]-R[XXX]-I[XXX]

1029C

The basic model number.

[X] The type of feedback

A - Specifies average voltage feedback. With average voltage feedback,

the controller varies the conduction angle (or ON time) of the SCRs

such that the average voltage applied to the load is proportional to

the command signal.

E - Specifies external feedback. The external feedback being

proportional to some parameter such as speed, current, etc. that is

ultimately being controlled by the action of the controller.

I - Specifies RMS current feedback. The load current is linearly controlled

with respect to the command signal.

P(XXXAMPS) - The letter P specifies power feedback and therefore the

load power is linearly controlled with respect to the command signal.

XXX equals amp level for control of power. MAX LOAD POWER =

(VOLTS)V x P(AMPS)

V - Specifies RMS voltage feedback. With RMS voltage feedback, the

controller varies the conduction angle (or ON time) of the SCRs

such that the RMS voltage applied to the load is proportional to the

command signal.

[XXX]V Operating Voltage

120, 208, 240, 277, 380, 415, 480 or 575 Vac

Note: unless otherwise specified, the controller is shipped with a

transformer that has primary voltage taps at:

240, 480 or 575 volts, 50/60 Hz.

[XXX]A Operating Current

50, 80, 120, 160, 200, 250, 300, 380, 425, 500, 600 or 750

(consult factory for 1000 & 2000 Amps)

IL[XXX] Current Limiting

Up to 105% of controller rating.

R[XXX] Run Command Signal

0/5Vdc, 4/20mA or Potentiometer

I[XXX] Idle Command Signal

0/5Vdc, 4/20mA or Potentiometer

Example:

1029C-A-480V-80A-IL75-R0/5V-IPOT

Will order a 1029C controller with average voltage feedback, rated @ 480 Volts, 80 Amps, current limit set at 75 Amps,

run command signal of 0 to 5Vdc and a potentiometer on the idle command input.

If a "SC(

VVV) term is included, it implies special calibration, meaning that the controller has been calibrated for a

maximum output of

(VVV) voltage rather than the rated (line) voltage. Contact factory for information.