Figure 22, Figure 21, Command connections (continued) – Precision Control Systems 3629C User Manual
Page 18
MODEL 3629C
14
04/10/2007
COMMAND CONNECTIONS (Continued)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
+ 1.75
POS NEG
NEG
ON #14
POS
ON #18
METERING THE OVER CURRENT TRIP SETTING.
Unless specified otherwise, the OVER CURRENT TRIP is
set at 175% of the controller current rating at the factory.
A reference output is available to assist in the recalibration
of this setting if this adjustment is accidentally changed.
POSITIVE 1.00 V output at terminal 18 with respect to
terminal 14 equals 100% of controller current rating.
POSITIVE 1.75 V output equals 175% of current rating.
For example; on the 3629C controller, POSITIVE 1.50
volts measured at terminal 18 with respect to terminal 14,
represents an over current trip setting of 150% of controller
current rating.
Figure 21. Over Current Trip metering output.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
- 1.050
POS NEG
NEG
ON #14
POS
ON #17
METERING THE CURRENT LIMIT SETTING.
Unless specified otherwise, the CURRENT LIMIT is set at
105% of the controller current rating at the factory.
A reference output is available to assist in the recalibration of
this setting if this adjustment is accidentally changed.
NEGATIVE 1.00 V output at terminal 17 with respect to
terminal 14 equals 100% of controller current rating.
NEGATIVE 1.05 V output will equal 105% original setting.
For example; on any 3629C controller, NEGATIVE 1.05 volts
measured at terminal 17 represents a current limit setting at
105% of the controller current rating.
Figure 22. Current Limit metering output.