Instantaneous value measurement: w range, Instantaneous value measurement – KYORITSU 6300 Quick Manual User Manual
Page 11

W
range
Safety first!
Turning on the instrument
Basic setting
Wiring
Instantaneous value
measurement
5. Instantaneous value measurement:
W
range
(Section 6)
● Measurement flow chart
● Displayed items on
W
range
Displayed parameters
Unit
Voltage (RMS) V : Average voltage of Vi
Vi : Voltage per phase
V
Current (RMS) A : Average current of Vi
Ai : Current per phase
A
Active power
P : Total active power
Pi : Active power per phase
Polarity: + (no mark) consumption,
- (minus) regenerating
W
Reactive power Q : Total reactive power
Qi : Reactive power per phase
Polarity: + (no mark) phase lag,
- (minus) phase lead
Var
Apparent power S : Total apparent power
Si : Apparent power per phase
VA
Power factor
PF : Total power factor
Pfi : Power factor per phase
Polarity: + (no mark) phase lag,
- (minus) phase lead
PF
Frequency
f : Frequency at V1
Hz
Neutral current In
**
: Current on a neutral line (only at three-phase 4-wire)
An
* i = 1, 2, 3
** :
The recorded/displayed In(neutral current) value will not be a true value in situations where
there is an earth leakage or leakage current flowing through the live conductors of the three
phase system that is being monitored using the Power Meter Model 6300.
SET UP
range
“ Setting 01” Wiring
“ Setting 02” Voltage range
“ Setting 03” Current range
“ Setting 04” Clamp sensor
“ Setting 05” VT ratio (if necessary)
“ Setting 06” CT ratio (if necessary)
− 9 −