Product summary and explanation – KYORITSU 6202 User Manual
Page 6

―
4
―
3.1 Product summary
Model 6200, 6202 perform tests and measurements in accordance with DIN
VDE 0701:2000 (Repair, modification and testing of electrical instruments) and
DIN VDE 0702:1995 (Repeat tests for electrical instruments). These standards
require to measure protective conductor resistance, insulation resistance and
equivalent leakage current of repaired or modified equipment or to test the
absence of voltage at the exposed metal parts of information technology
equipment and office machine. This instrument can perform voltage
measurement of main power supply, in addition to above measurements. For
M-6202, it can perform current consumption measurement.
This instrument is designed to check the electrical safety of the devices of
Safety Class I, Class II and Class III categories. As a guide IEC standard define
these three categories as follows:
Class l
:
Devices which have a functional insulation throughout and an earth
connected case. These are often described as earthed devices.
Class ll
:
Devices which have both functional and additional insulation where
any metal parts cannot become "Live" under fault conditions.
Class
Ⅲ:
Devices in which protection against electrical shock rely upon supply
from SELV circuit and in which hazardous voltage are not generated.
Note) SELV (safety extra low voltage) circuit is designed and protected that
under normal operating conditions, single fault condition and when basic
insulation is damaged, its voltage do not exceed a safe voltage.
3.2 Test range
MODEL 6200 and 6202 have following features.
3. Product summary and explanation
IL : Contact current measurement
IEL : Equivalent leakage current measurement
RINS : Insulation resistance measurement
RPE : Protective conductor resistance measurement
VOLT : Voltage measurement of mains power supply
ILINE : Current consumption measurement
M-6200
M-6202
O
O
O
O
O
×
O
O
O
O
O
O