beautypg.com

KYORITSU 4120A User Manual

Page 14

background image

― 12 ―

Fig.7

According to the international Standard IEC 60364 for TT system the
following condition shall be fulfilled for each circuit:

RA

50/Ia

Where:

¡

RA is the sum of the resistances of the local earth system R and
protection conductor connecting it to the exposed conductive part.

¡

50 is the max contact voltage limit (it could be 25V in particular cases)

¡

Ia is the current causing the automatic disconnection of the protective
device within 5 s.

When the protection device is a residual current device (RCD), Ia is the rated
residual operating current I

n.

For instance in a TT system protected by a RCD the max RA values are:

Note:

● The loop tester models 4120A / 4118A / 4116A measure the fault

loop impedance that is a value normally a little bit higher of RA.
But, if the electrical installation is protected considering the loop
impedance value, also the RA formula will be fulfilled.

Rated residual operating current I⊿n.

RA (at 50V)

10

5000
2500

30

1667

833

100
500
250

300
167

83

500
100

50

1000

50
25

mA

Ω
Ω

RA (at 25V)

The figure below shows in marked line the Fault loop impedance for TN
system.

This manual is related to the following products: