beautypg.com

Electrical connections, 3 supply voltage 3.6.4 electrical schema – KROHNE OPTIWAVE 7300 IECEx User Manual

Page 16

background image

3

ELECTRICAL CONNECTIONS

16

OPTIWAVE 7300 C

www.krohne.com

10/2010 - 4000176502 - AD IECEX OPTIWAVE7300 R02 en

3.6.3 Supply voltage

3.6.4 Electrical schema

CAUTION!
Do not ground the positive connection.

Current output terminal

Minimum voltage at output

terminal [VDC]

Maximum voltage at output

terminal [VDC]

1 (U

S1

)

20

1

36

1

2 (U

S2

)

2

10

1

30

1

1 Minimum voltage at output terminal for a current output of 22 mA
2 Optional. Use a second power supply. This power supply energizes current output terminal 2 only.

CAUTION!
Make sure that you connect the load resistor to the positive side.

Figure 3-4: Electrical schema for Ex d[ia] / Ex tD[iaD]-approved equipment (with galvanic isolation)

Figure 3-5: Electrical schema for Ex d[ia] / Ex tD[iaD]-approved equipment (without galvanic isolation)

1 Galvanically-isolated power supply (use a second power supply for optional terminal 2)
2 Power supply (use a second power supply for optional terminal 2)
3 Resistor for HART

®

communication

4 Non-Ex zone
5 Ex zone
6 |U| < 5 V