Page 15

background image

ELECTRICAL CONNECTIONS

3

15

OPTIWAVE 7300 C

www.krohne.com

10/2010 - 4000176502 - AD IECEX OPTIWAVE7300 R02 en

3.6 Ex d[ia] / Ex tD[iaD] equipment

3.6.1 General notes

Ex d[ia]- and Ex tD[iaD]-approved equipment have two separate compartments. The electronics
in the electronics block compartment are Ex ia / ExiaD-approved and the terminals
compartment is Ex d / Ex tD-approved.

3.6.2 How to connect the electrical cables

Cable entries are supplied on customer demand. If you supply the cable entries, this part must
have a degree of ingress protection IP≥6x (IEC 60529).

Load resistor

• Connect the load resistor to the positive terminal of the power supply
• Ground the negative connection.
• If the load resistor has to be connected to the negative terminal, the loop resistance must not

be more than 250 ohms.

Figure 3-3: Compartments in Ex d[ia]- and Ex tD[iaD]-approved equipment

1 Electronics block (Ex ia / Ex iaD) compartment
2 Terminal (Ex d / Ex tD) compartment

INFORMATION!
If you must open the electronics block compartment and remove the electronics blocks for
servicing, it is not necessary to disconnect the wires from the Ex d / Ex tD terminal.

INFORMATION!
The flamepath dimensions are better than the values specified in the International Standard
IEC 60079-1 (minimum length 14.5 mm and maximum gap 118

µ

m).

WARNING!
Use only Ex d-approved cable entries and plugs for Ex d applications. Use only Ex tD-approved
cable entries and plugs for Ex tD applications.