Electrical connections, 4 input/output connections – KROHNE TIDALFLUX 2300 F Ex EN User Manual
Page 20
4
ELECTRICAL CONNECTIONS
20
TIDALFLUX 2300 F
www.krohne.com
6/2013 - 7312442200 - AD EX TIDALFLUX 2300 - en - R02
4.4 Input/output connections
• IFC 300 converters are available in versions with intrinsically safe (Ex i) or non-intrinsically
safe (non-Ex i) inputs/outouts (I/O). Details of both versions (CG. no's and connection of
terminals) are listed in the IFC 300 handbook.
• The versions with non-Ex i I/O are listed in the IFC 300 handbook (title: alterable input/output
versions). The version basic I/O is also with non-Ex i I/O. The electrical data of the I/O circuits
with non-Ex i I/O are:
U
n
< 32 VDC and I
n
≤100 mA.
• The versions with Ex i inputs/outputs are listed in the IFC 300 handbook (title: Fixed, non-
alterable input/output versions), except the IFC 300 version basic I/O, last digits of CG. no.
100. This version is always with non-Ex i I/O.
The electrical data of the versions with Ex i I/O are listed below.
The following signal I/O connections are available as intrinsically safe:
The I/O circuits titled “Ex i I/O” and “Ex i Option” are always provided with type of protection
Intrinsic Safety (Ex ia). The I/O-circuits “Fieldbus I/O Profibus-PA” as well as “Fieldbus I/O
Foundation Fieldbus” can be provided with type of protection Intrinsic Safety.
I/O PCB
I/O PCB
I/O PCB
I/O PCB
CG nr.
CG nr.
CG nr.
CG nr.
(XYZ)
(XYZ)
(XYZ)
(XYZ)
I/O functions
I/O functions
I/O functions
I/O functions
Ex i I/O
300, 310, 320
Current output 4...20 mA with
HART passive (C and C-)
Ex ia IIC
U
i
= 30 V, I
i
= 100 mA, P
i
= 1.0 W
C
i
= 10 nF, L
i
= negligibly low
200, 210, 220,
300, 310, 320
Pulse/status output (D and D-)
200, 210, 220
Current output 4...20 mA with
HART active (C and C-)
Ex ia IIC
U
o
= 21 V, I
o
= 90 mA, P
o
= 0.5 W
Lineair characteristics
C
o
= 90 nF, L
o
= 2.0 mH
C
o
= 110 nF, L
o
= 0.5 mH
Ex i Option
220, 320
Current output 4...20 mA passive
(A and A-)
Ex ia IIC
U
i
= 30 V, I
i
= 100 mA, P
i
= 1.0 W
C
i
= 10 nF, L
i
= negligibly low
210, 220, 310,
320, D10, D20,
E10, E20
Pulse/status output / control input
(B and B-)
210, 310, D10,
E10
Current output 4...20 mA active
(A and A-)
Ex ia IIC
U
o
= 21 V, I
o
= 90 mA, P
o
= 0.5 W
Lineair characteristics
C
o
= 90 nF, L
o
= 2.0 mH
C
o
= 110 nF, L
o
= 0.5 mH
Fieldbus I/O D00, D10, D20
Profibus-PA
(C and C-, D and D-)
Ex ia IIC
U
i
= 24 V, I
i
= 380 mA, P
i
= 5.32 W
C
i
= 5 nF, L
i
= 10 μH
Suitable for connection to an
intrinsically safe fieldbus in
accordance with the FISCO model.
E00, E10, E20
Foundation Fieldbus
(C and C-, D and D-)