TECHNICAL DATA

6

27

OPTIFLUX 6000

www.krohne.com

11/2013 - 4001723703 - HB OPTIFLUX 6000 R03 en

Operating conditions

Temperature

Temperature

Temperature

Temperature

Process temperature

Seperate flow sensor: -40...+140°C / -40...+284°F

Compact with IFC 300 converter: -40...+140°C / -40...+284°F

Compact with IFC 050 - IFC 100 converter: -40...+120°C / -40...+248°F

For detailed information refer to

Temperatures

on page 20.

For Ex versions different temperatures are valid.

Please check the relevant Ex documentation for details.

Ambient temperature

-40...+65°C / -40...+149°F

Storage temperature

-50...+70°C / -58...+158°F

Pressure

Pressure

Pressure

Pressure

Ambient pressure

Atmospheric

Nominal flange pressure

For detailed information refer to

Dimensions and weights

on page 30.

Vacuum load

0 mbar / 0 psi

Chemical properties

Chemical properties

Chemical properties

Chemical properties

Physical condition

Electrical Conductive liquids

Electrical conductivity

Standard: ≥ 1 μS/cm

Demineralized water: ≥ 20 μS/cm

Permissible gas content

(volume)

IFC 050: ≤ 3%

IFC 100: ≤ 3%

IFC 300: ≤ 5%

Permissible solid content

(volume)

IFC 050: ≤ 10%

IFC 100: ≤ 10%

IFC 300: ≤ 70%

Installation conditions

Installation

Assure that the flow sensor is always fully filled.

For detailed information refer to

Installation

on page 11.

Flow direction

Forward and reverse

Arrow on flow sensor indicates positive flow direction.

Inlet run

≥ 5 DN

Outlet run

≥ 2 DN

Dimensions and weights

For detailed information refer to

Dimensions and weights

on page 30.