Technical data – KROHNE OPTIFLUX 4000 EN User Manual

Page 26

background image

6

TECHNICAL DATA

26

OPTIFLUX 4000

www.krohne.com

01/2011 - 4000818502 - HB OPTIFLUX 4000 R02 en

Measuring accuracy

Reference conditions

Flow conditions similar to EN 29104

Medium: water

Electrical conductivity: ≥ 300 μS/cm

Temperature: 10...30°C / 50...86°F

Inlet section: ≥ 5 DN

Operating pressure: 1 bar / 14.5 psig

Wet calibrated on EN 17025 accredited calibration rig by direct

volume comparison.

Accuracy curves

For detailed information on the measuring accuracy, see chapter

"Measuring accuracy".

Option: verification to MID MI-001

(Only in combination with IFC 300)

Option: calibration according to OIML R49

(Only in combination with IFC 300)

Related to volume flow (MV = Measured Value)

These values are related to the pulse / frequency output.

The additional typical measuring deviation for the

current output is ±10 μA.

With IFC 040 converter:

With IFC 040 converter:

With IFC 040 converter:

With IFC 040 converter:

v < 1 m/s / 3.3 ft/s: ± 5 mm/s

v > 1 m/s / 3.3 ft/s: ± 0.5 % of MV

With IFC 100 converter:

With IFC 100 converter:

With IFC 100 converter:

With IFC 100 converter:

DN2.5...6: ± 0.4% of MV + 1 mm/s

DN10...1200: ± 0.3% of MV + 1 mm/s

With IFC 300 converter:

With IFC 300 converter:

With IFC 300 converter:

With IFC 300 converter:

DN2.5...6: ± 0.3% of MV + 2 mm/s

DN10...1600: ± 0.2% of MV + 1 mm/s

DN1800...3000: ± 0.3% of MV + 2 mm/s

Repeatability

±

0.1% of MV, minimum 1 mm/s

Long term stability

±

0.1% of MV

Special calibration

On request.