3 measurement data, 4 status data, Operation – KROHNE OPTIFLEX 1300C FOUNDATION FIELDBUS User Manual
Page 8
4
OPERATION
8
OPTIFLEX 1300 C
www.krohne.com
02/2010 - 4000621501 - AD FF OPTIFLEX 1300 R01 en
4.1.3 Measurement data
Use a master and the DD - CFF files to configure the device for the network. Set the
measurement values (modules) that are regularly transmitted to the master device. The table
that follows gives a list of measurement data (each value has a status) that is available in this
sequence.
Measurement data
4.1.4 Status data
Foundation Fieldbus
Variable
Measurement variable
Unit
PRIM_VAL_TYPE_0
Level
1
Meter
PRIM_VAL_TYPE_1
Distance
1
Meter
PRIM_VAL_TYPE_2
Interface Level
2
Meter
PRIM_VAL_TYPE_3
Interface Distance
2
Meter
PRIM_VAL_TYPE_4
Layer
3
Meter
PRIM_VAL_TYPE_5
Interface Conversion
4
Cubic meter
PRIM_VAL_TYPE_6
Ullage Conversion
5
Cubic meter
PRIM_VAL_TYPE_7
Layer Conversion
6
Cubic meter
PRIM_VAL_TYPE_8
Level Conversion
7
Cubic meter
PRIM_VAL_TYPE_9
Level Mass
7
Ton (metric)
PRIM_VAL_TYPE_10
Distance Mass
7
Ton (metric)
1 if the "Application Mode" value (in the device Quick Setup menu) is set to "Interface only", this measurement is not
available. The message "Not_a Number (non signalling) is transmitted. The status is set to "Bad-Out of Service".
2 if the "Application Mode" value (in the device Quick Setup menu) is set to "Level only", this measurement is not avail-
able. The message "Not_a Number (non signalling) is transmitted. The status is set to "Bad-Out of Service".
3 if the "Application Mode" value (in the device Quick Setup menu) is set to "Level only" or "Interface only", this measure-
ment is not available. The message "Not_a Number (non signalling) is transmitted. The status is set to "Bad-Out of
Service".
4 if the "Application Mode" value (in the device Quick Setup menu) is set to "Level only" and there is no conversion table,
this measurement is not available. The message "Not_a Number (non signalling) is transmitted. The status is set to
"Bad-Out of Service".
5 if there is no conversion table, this measurement is not available. The message "Not_a Number (non signalling) is
transmitted. The status is set to "Bad-Out of Service".
6 if the "Application Mode" value (in the device Quick Setup menu) is set to "Level only" or "Interface only" and there is
no conversion table, this measurement is not available. The message "Not_a Number (non signalling) is transmitted.
The status is set to "Bad-Out of Service".
7 if the "Application Mode" value (in the device Quick Setup menu) is set to "Interface only" and there is no conversion
table, this measurement is not available. The message "Not_a Number (non signalling) is transmitted. The status is
set to "Bad-Out of Service".
CAUTION!
Monitor the status of the device. The device transmits a measurement value when the device
status is "good", "uncertain" or "bad". The status will tell you if the device measures correctly.